User manual
µC
2
SE process chiller +030220416 - rel. 2.2 - 25.01.2013
7.2 Variables accessible only by supervision
Par.
Description
Level
min
max
U.M.
Def.
Visibility
SVP CAREL
ModBus®
R/W
Variable type
r43 Heaters se
t
-point:
0=A4, A8, A11, P16, P19 absolute
1=A4, P16, P19 absolute, A8, A11 relative
2=A8, A11, P16, P19 absolute, A4 relative
3=P16, P19 absolute, A4, A8, A11 relative
4=A4, A8, A11 absolute, P16, P19 relative
5=A4 absolute, A8, A11, P16, P19 relative
6=A8, A11 absolute, A4, P16, P19 relative
7=A4, A8, A11, P16, P19 relative
F
07 -
0 -
121 328 R/W I
r45 Relative regulation maximum se
t
poin
t
D r46 176 °C/°F
30 -
84 84 R/W
A
r46 Relative regulation minimum se
t
poin
t
F
-40 r45 °C/°F
10 -
85 85 R/W
A
Firmware parameters: F - r*
H99 Software version D 0 99.9 in
t
- -
1 208
R
I
H97 Driver software version D 0 99.9 in
t
- V
3 210
R
I
H95 Expansion software version (I/O board) D 0 99.9 in
t
- -
149 356
R
I
- On-Off
0 = Off
1 = On
D01 -
0
64 64 R/W D
- Digital inpu
t
1 D 0 1 -
0
53 53
R
D
- Digital inpu
t
2 D 0 1 -
0
54 54
R
D
- Digital inpu
t
3 D 0 1 -
0
55 55
R
D
- Digital inpu
t
4 D 0 1 -
0
56 56
R
D
- Digital inpu
t
5 D 0 1 -
0
57 57
R
D
- Digital inpu
t
B4 D 0 1 -
0
58 58
R
D
- Digital output 1 D 0 1 -
0
59 59 R/W D
- Digital output 2 D 0 1 -
0
60 60 R/W D
- Digital output 3 D 0 1 -
0
61 61 R/W D
- Digital output 4 D 0 1 -
0
62 62 R/W D
- Digital output 5 D 0 1 -
0
63 63 R/W D
- Reset alarms D 0 1 -
0
78 78 R/W D
34