User manual

30
1 bar 1,5 bar 2 bar F08-F09
ENGLISH
µC
2
SE process chiller +030220416 - rel. 1.1 - 27.04.2010
Alarm settings: parameters (P*)
- Flow switch alarm delay when starting pump
P01: Establishes a delay in the recognition of the fl ow switch alarm when starting the pump (this allows the
ow-rate to stabilise). In the event of alarms, the compressors are stopped immediately, ignoring the times.
- Flow switch alarm delay in steady operation
P02: Establishes a delay in the recognition of the fl ow switch alarm in steady operation, so as to fi lter any
variations in fl ow-rate or air bubbles present in the water circuit. In the event of alarms, the compressors
are stopped immediately, ignoring the times.
- Low pressure alarm delay at compressor start
P03: Establishes a delay in the recognition of the low pressure alarm when the compressor starts, so as
to allow stable operating conditions to be reached. This delay is also counted when reversing the 4-way
valve in the refrigerant circuit.
- Part load in high pressure and low pressure in heat pump
P04: enable or disable the part load operation of the circuit in high pressure.
The function is valid if the unit is fi tted with tandem or capacity controlled compressors and pressure
transducers. In the event of high pressure alarms, that is, for values over P18 (hysteresis 0.5 bar), the
controller deactivates a load step in the circuit in question and waits 10 seconds. After this interval, if the
alarm is still active, the unit is stopped, otherwise it continues to operate in part load mode. In this situation,
the display shows the message PH1 and/or PH2, depending on the circuit. This condition remains active
until the pressure falls below the value corresponding to the maximum speed of the condenser fans
(F05+F06). Below this value, the unit reactivates the load step that had previously been deactivated.
P04=0: capacity control not activated
P04=1: capacity control activated for high pressure
P04=2: capacity control activated for low pressure
P04=3: capacity control activated for high and low pressure
With the unit operating in heat pump mode, due to low outside temperatures or the load the pressure may
fall and stop the unit due to the low pressure alarm. If the circuit has 2 compressor steps and the pressure
remains below the value of one bar for the time P22, the circuit can operate at part load. This capacity
control is not activated when the alarm comes from the digital input. In the event of low pressure, the
controller deactivates one step and if the pressure does not return above the threshold in 10 seconds, the
alarm is activated and the circuit is stopped. This function is valid for all units with pressure transducers.
- Alarm reset
P05: Enables automatic reset for all those alarms that normally feature manual reset (high pressure, low
pressure, fl ow switch/antifreeze) as per the following table:
P05= 0: (default) high pressure, low pressure and antifreeze (low temperature) with manual reset;
P05= 1: all the alarms with automatic reset;
P05= 2: high pressure and antifreeze (low temperature) manual, low pressure automatic;
P05= 3: high pressure manual, low pressure and antifreeze (low temperature) automatic;
P05= 4: high and low pressure manual, antifreeze (low temperature) automatic;
P05= 5: high and low pressure manual after the third activation in one hour*, antifreeze (low temperature)
automatic;
P05= 6: high and low pressure manual after the third activation in one hour*, antifreeze (low temperature) manual.
- Low pressure alarm with pressure probes
P07: P07=0: this function is disabled.
P07=1: if in heat pump mode the evaporator (external exchanger) pressure is less than 1 bar (and if the
presence of the condenser pressure probe is enabled), the low pressure alarm is activated (while still
considering the delay P03).
Note: P07=1 the LP digital inputs in heat pump are ignored.
- Select digital input ID1
P08= 0: none;
P08= 1: ow switch with manual reset (normally closed);
P08= 2: ow switch with automatic reset (N.C.);
P08= 3: general thermal overload with manual reset (N.C.);
P08= 4: general thermal overload with automatic reset (N.C.);
P08= 5: thermal overload circuit 1 with manual reset (N.C.);
P08= 6: thermal overload circuit 1 with automatic reset (N.C.);
P08= 7: thermal overload circuit 2 with manual reset (N.C.);
P08= 8: thermal overload circuit 2 with automatic reset (N.C.);
P08= 9: cooling/heating (open = Cooling, closed = Heating) if H06= 1;
P08= 10: cooling/heating with delays d12 and d13 (open = Cooling, closed = Heating) if H06= 1;
P08= 11: alarm signal with manual reset (N.C.);
P08= 12: alarm signal with automatic reset (N.C.);
P08= 13: second set point from external contact (cooling and heating), (normally open);
P08= 14: second cooling set point from external contact and heating from time band (N.O.);
P08= 15: end defrost from external contact circuit 1 (N.C.);
P08= 16: end defrost from external contact circuit 2 (N.C.);
P08= 17: end defrost from external contact circuit 1 (N.C.);
P08= 18: end defrost from external contact circuit 2 (N.C.);
P08= 19: condenser step 1 (N.O.);
P08= 20: condenser step 2 (N.O.);
P08= 21: condenser step 3 (N.O.);
P08= 22: condenser step 4 (N.O.);
P08= 23: remote ON/OFF.
*: the high and low pressure alarms are managed in the
same way both for the transducers and the pressure switches
(digital input); if the unit is in standby the count (3 times in
one hour) is reset.
note 1: if P08 is set to 10, the change in state considers the
times d12 and d13, and respects the compressor protection
times, both from the digital input and the keypad.
note 2: if the digital input is used to switch the unit ON/OFF
or change the operating mode, these functions are disabled
on the keypad.
note 3: ID5 for the condensing unit with reverse cycle has
the function of cooling/heating changeover
Fig. 5.b.b
all LP
pressure
Part load in low pressure
parz LP