User Guide

1
Tech Support (800) 989-2275 www.carlincombustion.com
Installing and Wiring
The 60200FR control must be installed and serviced only by a qualified service technician.
1. Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must
comply with applicable codes and ordinances.
2. Thermostat terminals (T-T, BV, CO) provide a current source. Never apply external power to these terminals under
any circumstances.
3. Alarm terminals provide a 24 VAC/VDC-rated dry contact, suitable for use with security/fire alarm systems.
Mounting
The control may be mounted on a 4" x 4" junction box in any convenient location on the burner, furnace or wall.
The location must not exceed the ambient temperature limit, 140°F.
Wiring
Wiring must comply with local and national electrical codes, and with the wiring diagram.
SEE WIRING DIAGRAMS ON NEXT PAGE
Model 60200FR
Gas Primary Control
Data Sheet
Power input (red/white wire) 120 VAC, 60 HZ, 9 VA
Limit circuit input (black wire) 120 VAC, 60 HZ
Motor load (orange wire) 10 FLA / 60 LRA
(reduce by valve and ignition load)
Ignitor load (blue wire) 120 VAC, 60 HZ, 500 VA
Valve load (violet wire) 2 amps
Aux
120 VAC, 1 amp
Alarm contacts (dry contacts) 24V, AC/DC, 2A
Operating temperature limits
+32°F to +140°F
Storage temperature limits
-40°F to +185°F
Thermostat
24 VAC, 0.1A
Blocked Vent
12 VDC. 2mA
CO
12 VDC. 2mA
Agencies
UL recognized (US & Canada)
Programmable, Micropro-
cessor Based Gas Burner
Primary Controls
On-Board LCD Screen
Easy to Understand Icons for Inputs and Outputs
Displays micro-amp Flame reading
Display operational information
Fault History records last 50 fault
cycles to aid the technician in
troubleshooting
• Field Settable Timings
• Pre-purge (0, 10, 30, 90)
• Trial for Ignition Time (4, 6)
• Post-Purge (0, 10, 15, 30, 60, 120)
Number of Recycles allowed
(0, 1, 3)
• Serviceman Reset Protection (3)
Low Voltage Terminals
TT (can be programmed as Used or Not used)
Blocked Vent input (contact closure, functions as a low
voltage limit)
CO input (contact closure) required to start C.F.H .,
lockout if not detected during run
Alarm output (dry contacts) 24VAC/DC