Datasheet
Model
Range code
Measurement
Power supply
Setpoints
Options
Specifications are subject to change without notice 1
•3-dgt µP-based indicator for
AC currents or voltages
• Selectable CT/VT primary range
• Panel mounting
• 72 x 72 mm
• Degree of protection (front): IP 50 (IP 65 on request)
Product Description
Ordering Key
DI3-72AV5AD0XX
3-dgt µP-based meter with
double input for AC currents
or voltages. With 20 selectable
primary CT/VT ranges. The
housing is for panel mounting
and ensures a degree of
protection (front) of IP 50 (IP
65 on request).
Panel Meters and Controllers
AC Ammeter or Voltmeter
Type DI3-72 AV1/AV5
Type Selection
Power supply
A:
24 VAC, -15% +10%,
50/60 Hz
1)
B: 48 VAC, -15% +10%,
50/60 Hz
1)
C: 115 VAC, -15% +10%,
50/60 Hz
1)
D: 230 VAC, -15% +10%,
50/60 Hz (standard)
Range code
AV1:
1 A/100 V
Standard cur-
rent/voltage
AV5: 5 A/500 V
Standard cur-
rent/voltage
See Range Table
1)
Power supply on request
Options
XX:
None (standard)
EX: Degree of protection
IP 65
Operating temperature 0° to 50°C (32° to 122°F)
(R.H. < 90% non-condensing)
Storage temperature -10° to 60°C (14° to 140°F)
(R.H. < 90% non-condensing)
Insulation reference voltage 300 V
rms
to ground
Dielectric strength 4000 V
rms
for 1 minute
Noise rejection
CMRR 100 dB, 40 to 60 Hz.
EMC IEC 60801-2, IEC 60801-3,
IEC 60801-4 (level 2),
EN 50 081-1, EN 50 082-1.
Safety standards EN 61 010-1, IEC 61010-1,
VDE 0411
Connector Screw-type
Housing
Dimensions 72 x 72 x 75 mm
Material ABS,
self-extinguishing: UL 94 V-0
Degree of protection Front: IP 50 (IP 65 on request)
Weight Approx 250 g
Approvals CE, CSA
General SpecificationsInput Specifications
Rated input
5A/500 VAC, 45 to 400 Hz
(1A/100 VAC on request)
Overload protection
Cont. Current: 1.2 x rated input
Voltage: 1.2 x rated input
For 1 s Current: 5 x rated input
Voltage: 2 x rated input
Accuracy
(@ 25°C ± 5°C, R.H. ≤ 60%) ± 0.5% f.s., ± 1 dgt
Temperature drift ± 350 ppm/ºC
Display 7-segment LED, h 14.2 mm,
3 digits
Sampling rate 1 time/s
Indication
Max. 999
Min. 000
500 VAC range Scale suppressionup to 5% f.s.
Other ranges Scale suppressionup to 3% f.s.
Over range EEE
Input range selection DIP-switch selectable
Decimal point position DIP-switch selectable