Datasheet

Specifications are subject to change without notice (16.10.06) 1
Monitoring Relays
Product Description
Ordering Key
Housing
Function
Type
Item number
Output
Power supply
TRMS 3-phase over and under voltage,
phase sequence and phase loss monitoring relays
Detect when all 3 phases are present and have the
c
orrect phase sequence (except for N versions)
Available versions (W4) supplied between phase and
n
eutral
Detect if all the 3-phase-phase or phase-neutral volt-
ages are within the set limits
Upper and lower limits separately adjustable
Measure on own power supply
Selection of measuring range by DIP-switches
Adjustable voltage on relative scale
Adjustable delay function (0.1 to 30 s)
Output: 8 A SPDT relay N.E.
For mounting on DIN-rail in accordance with
D
IN/EN 50 022 (DPB01) or plug-in module (PPB01)
22.5 mm Euronorm housing (DPB01)
or 36 mm plug-in module (PPB01)
LED indication for relay, alarm and power supply ON
Type Selection
Mounting Phase sequence Output Supply: Supply: Supply:
detection 208 to 240 VAC 380 to 415 VAC 380 to 480 VAC
DIN-rail yes SPDT DPB 01 C M23 DPB 01 C M48 W4 DPB 01 C M48
Plug-in yes SPDT PPB 01 C M23 PPB 01 C M48 W4
Plug-in yes SPDT PPB 01 C M48
DIN-rail no SPDT DPB 01 C M23 N DPB 01 C M48 N W4 DPB 01 C M48 N
Plug-in no SPDT PPB 01 C M23 N PPB 01 C M48 N W4
Plug-in no SPDT PPB 01 C M48 N
Input
L1, L2, L3, N DPB01: Terminals L1, L2, L3, N
PPB01: Terminals 5, 6, 7, 11
Measure on own supply
Note: Connect the neutral only
if it is intrinsically at the star
centre
Measuring ranges
208 to 240 VAC
177 to 275 V
L-L
AC
M23 versions
380 to 415 VAC 323 to 475 V
L-L
AC
PPB01CM48
PPB01CM48N
D/P PB01CM48W4
D/P PB01CM48NW4
380 to 480 VAC 323 to 550 V
L-L
AC
DPB01CM48
DPB01CM48N
True RMS 3-Phase, 3-Phase+N, Multi-function
Types DPB01, PPB01
Input Specifications
DPB 01 C M23
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss, over and under voltage
(separately adjustable set
points) with built-in time
delay function.
Supply ranges from 208 to
480 VAC covered by two
multivoltage relays.
D
PB01
PPB01
Ranges
Upper level +2 to +22%
of the nominal voltage
Lower level -22 to -2%
of the nominal voltage
Note: The input voltage
must not exceed the maximum
rated voltage or dr
op below
the minumum rated voltage
r
eported above.
Hyster
esis
Set points from 2 to 5% 1%
Set points from 5 to 22% 2%