Datasheet
Specifications are subject to change without notice EM24 DIN DS 260315 1
Specifications are subject to change without notice EM24 DIN DS 260315 1
• Class 1 (kWh) according to EN62053-21
• Class B (kWh) according to EN50470-3
• Class 2 (kvarh) according to EN62053-23
• Accuracy ±0.5 RDG (current/voltage)
• Energy analyzer
• Instantaneous variables readout: 4 DGT
• Energies/gas/water readout: 8 DGT
•
System variables: VLL, VLN, Admd max, VA, VAdmd, VAd-
md max, W, Wdmd, Wdmd max, var, PF, Hz, Phase-
sequence.
• Single phase variables: VLL, VLN, A, VA, W, var, PF
• Energy measurements: total and partial kWh and kvarh or
based on 4 different tariffs; single phase measurements
• Gas, cold water, hot water, kWh
remote heating
mea-
surements
• Hour counter (6+2 DGT)
• TRMS measurements of distorted sine waves (volt-
ages/currents)
• Self power supply (AV2-AV9 inputs)
• Auxiliary power supply (AV5-AV6 inputs)
•
3 digital inputs for tariff selection, DMD synch or gas/
water (hot-cold) and remote heating metering (on request)
• 2 digital outputs for pulses or for alarms or as a mix of
them
• Dimensions: 4-DIN modules
• Protection degree (front): IP50
Product Description
Three-phase energy analyzer
with built-in configuration
joystick and LCD data dis-
playing; particularly indicat-
ed for active and reactive
energy metering and for cost
allocation. Housing for DIN-
Energy Management
Energy Analyzer
Type EM24 DIN
• RS485 serial output (MODBUS-RTU), iFIX SCADA com-
patibility
• M-bus communication port (option M1)
• Dupline communication capability (option DP)
• Application adaptable display and programming proce-
dure (Easyprog function)
• Easy connections management
• Certified according to MID Directive (option PF):
see “how to order” below
• Other versions available (not certified, option X):
see “how to order” on the next page
rail mounting with IP50
(front) protection degree.
Direct connection up to 65A
and by means of external
current and potential trans-
formers.
Moreover the meter can be
provided with digital outputs
that can be either for pulse
proportional to the active
(imported and exported) and
reactive energy being mea-
sured or for alarm outputs.
In alternative the RS485
communication port and 3
digital inputs or Dupline port
and 3 digital inputs or the
M-bus communication port
are available as an option.