Datasheet
8 Specifications are subject to change without notice EM24 DIN DS 260315
EM24 DIN
Self supplied version AV9 models
“XX” and “O2” options
only: -20% +15%, 48-
62Hz. “R2”, “M1” and “IS”
options only: -15% +10%,
48-62Hz.
AV2 model:
“XX”, “O2”, “IS” and “DP”
options: -15% +15%, 48-
62Hz. In case of 3-phase
system, 4-wire connection:
113 to 265V. In case of 3-
phase system, 3-wire con-
nection: 196 to 460V.
Note The instruments provided
with “IS” and “R2” options
work only if all the voltage
inputs are connected (3-
phase and neutral) if a 1-
phase connection has to
be performed the L1 and
L2 voltage inputs have to
be short circuited. The
instrument provided with
“O2” option, working in a
3-phase system with neu-
tral may work also if one or
two phases are missing.
Auxiliary power supply AV5-AV6 modules:
L: 18 to 60VAC/DC;
D: 115VAC/230VAC
(-/+15%) from 48 to 62Hz
Power consumption
AV9-AV2 models ≤ 20VA/1W
AV9-AV2 models
(IS and DP option only) ≤ 12VA/2W
AV5-AV6 models ≤ 2VA/2W
Power supply specifications
supply input: 1kV
Radio frequency suppression According to CISPR 22
Standard compliance
Safety IEC60664, IEC61010-1
EN60664, EN61010-1
EN62052-11.
Metrology EN62053-23, EN50470-3.
MID ”annex MI-003”
Pulse output DIN43864, IEC62053-31
Approvals CE, cULus listed (AV5, AV6
options only), MID (PF
option only)
Connections Screw-type
Cable cross-section area
AV2-AV9 models measuring inputs max.
16 mm
2
; min. 2.5 mm
2
(by
cable lug). Min./Max.
screws tightening torque:
1.7 Nm / 3 Nm
Other inputs: 1.5 mm
2
Screws tightening torque:
0.5 Nm
Cable cross-section area
AV5-AV6 models Max. 1.5 mm
2
Screws tightening torque:
0.5 Nm
Housing DIN
Dimensions (WxHxD) 71 x 90 x 64.5 mm
Material Nylon PA66,
self-extinguishing: UL 94 V-0
Mounting DIN-rail
Protection degree
Front IP50
Screw terminals IP20
Weight Approx. 400 g (packing
included)
Operating temperature -25°C to +55°C (-13°F to
131°F) (R.H. from 0 to 90%
non-condensing @ 40°C)
according to EN62053-21,
EN50470-1 and EN62053-
23
Storage temperature -30°C to +70°C (-22°F to
158°F) (R.H. < 90% non-
condensing @ 40°C)
according to EN62053-21,
EN50470-1 and EN62053-
23
Installation category Cat. III (IEC60664,
EN60664)
Insulation (for 1 minute) 4000 VRMS between
measuring inputs and
power supply
4000 VRMS between power
supply and RS485/digital
output
Dielectric strength 4000 VRMS for 1 minute
Noise rejection CMRR 100 dB, 48 to 62 Hz
EMC According to EN62052-11
Electrostatic discharges 15kV air discharge
Immunity to irradiated Test with current: 10V/m
from 80 to 2000MHz
Electromagnetic fields Test without any current:
30V/m from 80 to 2000MHz
Burst On current and voltage
measuring inputs circuit:
4kV
Immunity to conducted
disturbances 10V/m from 150KHz to
80MHz
Surge On current and voltage
measuring inputs circuit:
4kV; on “L” auxiliary power
General specifications