Parameter Description
Roller blind control
(Decentralized Up-Down)
Roll time Insert the times (seconds) for which the motor is to run in each direction. The
value must be within 0 and 255 s.
The selected time interval should ensure that the roller blinds can reach the end
positions in both directions where an end position contact must switch the
motor off. Intermediate values allows shadow, for example. But it should be
ensured that the roller blind is in one of the end positions before start.
The entered roll time is overwritten by the roll time of the master.
Reverse delay Enter the delay time (milliseconds) before the roller blind changes direction. The
value should lie between 500 and 2000 ms.
Tilting blinds This option allows adjustment of tilting blinds. The function stops within the first
three seconds after the key is released.
The tilting blinds option must be activated if you want to define for how long the
roller blinds must run in the opposite direction after expiry of the roll time
Address By activation of the entered channel address, the roller blind runs in the selected
direction for the entered roll time. As long as the indicated priority channel is set,
input signals on the roller blind channels are ignored.
Note: The priority channel also overrides the master control.
Priority A channel or flag can be entered by which the up- or down-direction of the roller
blinds is given priority