Datasheet

9
Carlo Gavazzi Automation S.p.A.
ICB12, ICB18 & ICB30 IO-Link 3-wire DC
ICB12, ICB18 & ICB30 IO-Link 3-wire DC DS EN21/05/2018
IO-Link mode:
Yellow LED Output Description
OFF / ON SIO Shows SIO status if no short circuit or temperature errors.
Blinking
f: 2 Hz Short-circuit or overload
f: 1 Hz Temperature alarm (if enabled)
Disabled - Possibility to disable the LED
Green LED:
LED is ON for 0.75 s and OFF for 0.075 s
Possibility to disable the LED
Environmental
Ambient temperature for cable ver-
sions
Operating: -25° to +70°C (-13° to +158°F)
Storage: -30° to +80°C (-22° to +176°F)
Ambient temperature for plug ver-
sions
Operating: -40° to +70°C (-40° to +158°F)
Storage: -40° to +80°C (-40° to +176°F)
Ambient humidity
Operating: 35% to 95%
Storage: 35% to 95%
Vibration
10 to 55 Hz, amplitude 1.0 mm; sweep cycle 5
min; in X, Y and Z direction
IEC 60068-2-6
Shock 30 G /11 ms. 10 shocks in X, Y and Z direction IEC 60068-2-27
Rough handling shocks 2 times from 1m, 100 times from 0.5m IEC 60068-2-31
Degree of protection IP67 IEC 60529; EN 60947-1
Compatibility and conformity
EMC protection
IEC 61000-4-2 Electrostatic discharge
8 kV air discharge
4 kV contact discharge
IEC 61000-4-3 Radiated radiofre-
quency
3 V/m (ICB30: 12 V/m)
IEC 61000-4-4 Burst immunity 2 kV (ICB30: 4 kV)
IEC 61000-4-6 Conducted radio fre-
quency
3 V (ICB30: 10 V)
IEC 61000-4-8 Power frequency mag-
netic elds
30 A/m
MTTF
d
ICB12: 3963 years @50°C (122°F)
ICB18: 3945,2 years @50°C (122°F)
ICB30: 3479,3 years @50°C (122°F)
Approvals
®
CCC is not required for products rated ≤ 36 V