CARLO GAVAZZI A u t o m a t i o n C o m p o n e n t s IN G C A R LO G A V A Z Z I PQT-90: Modular network power quality transducer Harmonic analysis; Energy meters; Plug and play module system; SMS reception and transmission. These are only a few among the functions of PQT-90. What’s more, Carlo Gavazzi means ISO9001 certification, a working experience of many decades and a world-wide organization. All this because we want our customers to have the top products and the top service.
2 Warnings PQTSoft Remote and Network, PQT-90 modular quality network transducer, Instruction manual: FW rev. 01 CARLO GAVAZZI Controls SpA We suggest you to keep the orginal packing in case it is necessary to return the instrument to our Technical Service Department. In order to achieve the best results with your instrument, we recommen you to read this instruction manual carefully.
Index ■ PQTSof Remote setup PQT-90 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . ■ Overall dimensions, DIN-rail mounting . . . . . . . . . . ■ Position of slots and relevant modules . . . . . . ■ Connection of optional modules . . . . . . . . . . . ■ Electrical diagrams . . . . . . . . . . . . . . . . . . . . . Useful info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ■ Data logging operating principle and duration ■ Appl. bar: meaning of the icons . . . . . . . .
6 Setup PQTSoft Remote 7 Setup PQTSoft Remote ■ PQTSoft Remote in brief PQTSoft Remote has been conceived to program PQT-90 by means of a data transmission from the PC to the instrument via RS232 or RS485 serial interface. The choice between one interface or the other is therefore very important for the correct operation of the instrument as shown by the following figure: Local single PQT connected to the PC by RS232 serial port RS232 SIU-PC ...
8 Configuration PQTSoft Remote ■ Main menu 1 12345678- 2 4 3 5 9 Configuration PQTSoft Remote PQTSoft Remote manages a configuration archive that may be selected at any time. At first, when the software has just been installed, this file is empty. [1] Click on new configuration to start the programming procedure of PQT90. [2] It allows to load from PQT-90 the pre-existing programming and to modify it, if required. [3] Close the window without modifications. 6 7 8 ❑ Instrument composition...
10 Configuration PQTSoft Remote SMS messages when an alarm occurs. To carry out the data download, in this case, it is necessary to use the RS485 serial module. [3] Click this button to continue the configuration of PQT-90. The following windows will vary according to the modules selected in the box “Instrument composition...” (see previous page). ❑ Instrument working mode, clock and system setup 1 7 PQTSoft Remote 3 5 6 6 [1] Enables the energy metering.
12 Configuration PQTSoft Remote ❑ Digital input working mode setup 13 Configuration PQTSoft Remote and C2 are not available if PQT-90 is supplied with analogue measuring inputs AQ1018 or AQ1019. ❑ Harmonics analysis and digital filter setup [1] Enables the harmonic analysis on the selected phases, 1 4 2 3 6 5 7 1 8 [1] Enables digital input A1 (input 1 of the digital input module installed in slot A of PQT-90); [2] Enables digital input A1 working mode: “Gas meter” or “kWh- meter”.
14 Configuration PQTSoft Remote • COEFFICIENT: if the new value acquired by the instrument is within the action range of the filter, then the new displayed value will result from the sum of the previous value (A) to the variation (B) divided by the filtering coefficient (C), that is: [(A) + (B/C)]. As a consequence, a value higher than this coefficient, will result in a higher settling time and therefore a higher stability.
16 Configuration PQTSoft Remote ❑ Logging variables selection and dmd power calculation PQTSoft Remote 17 Configuration instrument calculates the dmd value and updates it every 15 minutes. FLOATING SELECTION: if for example the value “15 minutes” is selected, the instrument calculates the dmd value and updates its value at first after 15 minutes and then every minute generating a window whose width corresponds to 15 minutes and shifts by units of 1 minute.
18 Configuration PQTSoft Remote ❑ Tariffs and installed power setup PQTSoft Remote Configuration 19 ❑ Dual tariff setup 5 2 1 1 4 3 2 This function allows the user to choose the type of management of the energy meters. [1] Selects the type of tariff to be applied. “Single tariff”: the energy meters are set according to a single tariff which is the same for the whole year.
20 Configuration PQTSoft Remote a) It’s possible to divide the day into up to eight daily different time periods and up to four different tariffs as shown below: trf1 20 22 24 2 trf1 4 18 + kWh - kWh + kvarh - kvarh 8 14 12 10 trf2 + kWh - kWh + kvarh - kvarh 21 ❑ Multitariff setup 6 1 + kWh - kWh + kvarh - kvarh 6 16 Configuration PQTSoft Remote 1 T 2 4 3 5 2 4 3 5 2 The measured energy (partial energy) is placed in TARIFF 1 when the time period is from midnight to 8:00, in
22 Configuration PQTSoft Remote The WINTER and SUMMER time periods are conventional seasons mainly used to manage in the best way the different energy costs during the year. The reminds at steps a), b), c) d) on page 20 are also valid for the MULTI TARIFF function. PQTSoft Remote Configuration 23 ❑ Multitariff setup with digital inputs In the SINGLE TARIFF, only one period exists, referred to the whole year. In the DUAL TARIFF, the “year” can be divided into two periods: whole year and holidays.
24 Configuration PQTSoft Remote ❑ Digital output setup PQTSoft Remote 25 Configuration “Remote control”: makes it possible to control the digital outputs by means of the RS485/RS232 serial port instead of using the instrument. The outputs can be activated by means of a PC or PLC by means of specific commands. [2] Selects whether the event logging in the PQT-90 is to be activated or deactivated. 2 1 Where “DO...” shows the module and output to which the window refers.
26 Configuration PQTSoft Remote ❑ Digital output alarm setup PQTSoft Remote 27 Configuration energized and it’s de-energized in case of alarm. Normally de-energized: the output is normally de-energized and it’s energized in case of alarm. ❑ Analogue output alarm setup 3 1 2 4 1 5 2 6 [1] Selects the alarm working mode for the digital output. [2] Selection of activation or deactivation of the event logging of PQT-90. [3] Selects the variable to be checked.
28 Configuration PQTSoft Remote erated by the measured value (“max. input value”). “Min. output value”: value expressed as % of the zero of the output range (0-20mA, 0-10V, etc.) that is generated by the minimum measured value (“min. input value”).
30 ❑ Configuration PQTSoft Remote PQTSoft Remote [5] SMS messages for alarm deactivation: type the messages to be sent when the alarms are deactivated (there’s a max. number of characters available terminated which the user will not be allowed to continue typing the message). In any case, the user who will receive the message on his mobile phone will be able to read not only the preset text, but also date and hour relating to the event. Set SMS messagges and telephone numbers 1 Max.
32 Transmission of configuration PQTSoft Remote ❑ End of the configuration 33 Transmission of configuration PQTSoft Remote ❑ Communication setup After the configuration of all the PQT-90 parameters, press the key “End”. The new configuration will be added to the list of the configurations archive where you can select it and transmit it to the instrument. 1 ❑ Transmit the configuration 2 [1] Choose the mode and connection type (see also “PQTSoft remote” on page 6).
34 Transmission of configuration PQTSoft Remote ❑ Selection of phone numbers and setting of dialling 35 Transmission of configuration PQTSoft Remote ❑ Network address and warning messages properties 1 1 2 2 3 If in the “Communication setup” dialog box the option “modem” has been selected, then also the telephone number to be dialled by PQTSoft for the modem connection with the instrument will have to be selected. [1] Click the contact to select it.
36 ■ Last functions PQTSoft Remote Last functions PQTSoft Remote 37 ❑ Selection of connections and setting of dialling properties Reset of partial and total meters Reset all the energy, water and gas total and partial meters. After clicking on the function button on the main menu bar, set the type of communication, as explained from page 33. At the following window: [1] Select if the reset command is to be carried out for all the instruments located on the network or only on a single instrument.
38 Last functions PQTSoft Remote 1 2 4 3 5 [1] Type the name of the contact [2] Type the telephone number of the contact [3] Type the name of the data file folder (where all the files of data downloaded from the instrument will be saved) [4] Type the number of PQT located on the network. [5] If selected, PQTSoft will dial this contact when the “automatic reading” working mode will be active.
40 Installation 41 Installation PQT-90 Instruction manual PQT-90 Instruction manual 2 First extract the central dummy module and then all other modules. ■ Preliminary Operations Make sure that the supplied modules are placed in the correct slots as shown on the labels placed on the modules and as described on the following pages. A wrong insertion of the modules may damage the instrument.
42 Installation 43 Installation PQT-90 Instruction manual PQT-90 Instruction manual ■ Position of the slots and relevant modules DESCRIPTION A Single analogue output ✓ Dual analogue output ✓ C D PU PS IM B D C Single relay output ✓ ✓ Open collector single output ✓ ✓ Dual relay output ✓ ✓ Dual open collector output ✓ ✓ RS232 serial output PU PS ✓ ✓ RS485 serial output A B IM ✓ ✓ Quadruple open collector output ✓ 3 digital inputs 3 digital inputs + AUX ✓ ✓ ✓ Power suppl
44 Installation PQT-90 Instruction manual ■ Optional modules connections ❑ Digital inputs ❑ Digital input modules AQ1038 3 digital inputs Connection by means of NPN transistor. AQ1042 Digital inputs module. AQ1042 3 digital inputs + aux Connection by means of PNP transistor. AQ1042 Digital inputs module. ❑ Serial output modules AR1034 RS485 Interface AR1041 RS232 Interface + RTC+ 2Mb Data Memory Connection by contacts. Digital inputs module AQ1042.
46 Installation ❑ Relay outputs AO1058 Single relay outputs. 47 Installation PQT-90 Instruction manual PQT-90 Instruction manual ❑ Analogue outputs AO1035 Dual relay outputs. 1 analogue output (mA) 2 analogue outputs (mA) ❑ Open collector outputs AO1059 open collector single output. AO1036 open collector dual output. This diagram is valid also for the single output open collector module.
48 Installation 49 Installation PQT-90 Instruction manual PQT-90 Instruction manual ■ Electrical diagrams ❑ Three-phase, 3/4 wires, Balanced load ❑ RS485/422 (AR1034) Serial port 4-wire connection. Additional devices provided with RS485/422 (that is RS 1,2,3,...N) are connected in parallel. Direct connection (3-wire system) CT connection (3-wire system) CT and VT connection (3-wire system) Direct connection (4-wire system) 2-wire connection.
50 ❑ Installation Installation PQT-90 Instruction manual CT and VT connection (4-wire system) ❑ Three-phase, 4-wire connection, unbalanced load Direct connection (4-wire system) 51 ❑ Three-phase, 3/4 wire connection, unbalanced load Three-phase, 4-wire connection, balanced Load CT connection (4-wire system) PQT-90 Instruction manual CT and VT connection (4-wire system) ❑ ARON connection, Three-phase, 3 wires, Unbalanced load ARON CT connection (3-wire system) CT connection (4-wire system) 40
52 Installation ❑ 3-phase, 3-wire conn. 53 Useful info PQT-90 Instruction manual ❑ Single phase connect. PQT-90 Instruction manual ■ Data logging operating principle and duration The data logging duration depends on the number of variables that you want to log (from 1 to 8), from the selected integration time (from 1 to 60 minutes) and from the activation, if any, of the max./min. logging for each time interval.
54 Useful info Useful info PQT-90 Instruction manual Avg values PQT-90 Instruction manual 4 Sel. variables 2 Sel. variables Time Data logging duration Data logging duration intervals (min.) DAYS WEEKS YEARS DAYS WEEKS YEARS 1 122 17 81 12 5 610 87 1.7 407 58 1.1 10 174 3.4 814 116 2.2 15 262 5.0 174 3.4 20 349 6.7 232 4.5 25 436 8.4 291 5.6 30 523 10.1 349 6.7 35 610 11.7 407 7.8 40 697 13.4 465 8.9 45 785 15.1 523 10.1 50 872 16.8 581 11.2 55 959 18.4 639 12.3 60 20.1 697 13.
56 Useful info Useful info PQT-90 Instruction manual ■ Application bar: meaning of the icon When the PC is going to start the connection with the remote instrument, one icon appears on the application bar [1] indicating the status of the connection. [1] Represents a modem where two “green LEDs” flash alternately during RX and TX between a PC and a PQT.
58 Useful info 59 Technical features PQT-90 Instruction manual The variables measured by the instrument are correct if the inputs have been connected according to the right polarities (see figure below). Should the connection not be conforming to the right polarities, measuring and retransmission errors may occur, both due to the wrong direction of the current flowing in the primary/secondary of the ammeter transformer being connected.
60 Technical features Technical features PQT-90 Instruction manual ±0.5% (RDG + FS) (PF 0.5 L/C, 0.1 to 1.2 In, range AV5) or ±1% RDG (PF 0.5 L/C, 0.1 to 1.2 In, range AV5) Apparent power (@ 25°C ± 5°C, R.H. ≤ 60%): ±0.5% (RDG + FS) (0.1 to 1.2 In, range AV5) or ±1% RDG (0.1 to 1.2 In, range AV5). Energies (@ 25°C ± 5°C, R.H. ≤ 60%): Active: class 1 according to EN61036. Reactive: class 2 according to EN61268, Ib: 5A, Imax: 6A 0.1Ib: 500mA Start-up current: 20mA Un: 240V (AV5), 400V (AV7).
62 Technical features Technical features PQT-90 Instruction manual Static (writing only): all configuration parameters, energy reset, activation of digital outputs. Data format: 1 start bit, 8 data bit, no parity/even parity/ odd parity, 1 stop bit. Baud rate: 9600 bit/s. Insulation by means of optocouplers, 4000 VRMS output to measuring input, 4000 VRMS output to power supply input. RS232 (on request): bidirectional (static and dynamic variables). Connections: 3 wires, max. distance: 15m.
64 Technical features Technical features PQT-90 Instruction manual Transformer ratio: up to 6000 (CT up to 30kA). Up to 6000 (VT up to 600kV). Filters: Filter operating range: 0 to 99.9% of the input electrical scale. Filtering coefficient: 1 to 255 Filter action: display, alarms, serial outputs (fundamental variables: V, A, W and their derived ones). Event logging: only with RS232+RTC+Data memory. Type of data: alarms and max./min. (max.
66 ■ Technical features Technical features PQT-90 Instruction manual Harmonic distortion analysis Analysis principle: FFT Harmonic measurement: current, up to the 50th harmonic Voltage, up to the 50th harmonic. Type of harmonics: THD (VL1) THD odd (VL1) THD even (VL1). Same is for the other phases: L2, L3. THD (AL1) THD odd (AL1) THD even (AL1). Same is for the other phases: L2, L3.
68 Setup PQTSoft Network ■ Installing PQTSoft Network When the CD-ROM is inserted in the drive, the installation software is automatically executed (the CD-ROM drive is to be enabled) and the dialog box on the left is displayed. If the setup will not run, select “explore CDROM” and manually execute the application double clicking the icon . Then, choose the operating system and the desired language from the drop-down menus (see figure above).
70 Setup PQTSoft Network 71 Setup PQTSoft Network Local single PQT connected to the PC by RS232 serial port. RS232 SIU-PC ... MAX255 RS232 RS485 RS485 Maximum 255 PQT’s in an RS485 local network connected to the PC by RS232 thanks to the RS485-RS232 SIU-PC converter. MODEM RS232 MODEM Telephone network RS232 ... MAX100 Max. 100 remote single PQT’s (PQTSoft can manage max.
72 Configuration PQTSoft Network 73 Configuration PQTSoft Network ■ Configuration of the automatic data download ■ Main menu This function allows the configuration for an automatic reading, at programmable dates, of the data logged in the data logger of PQT-90 (AR1041). PQTSoft will question the instrument on the programmed dates. 1 2 3 4 5 6 7 8 9 10 1) Drop-down menu of the functions.
74 ❑ Configuration PQTSoft Network Selection of phone numbers and dialling properties 75 Configuration PQTSoft Network ❑ Folder selection for data files, counter file and event file 1 1 2 3 2 2 1 1 2 If in the “Communication setup” dialog box the option “modem” has been selected, then also the telephone number/s to be dialled by PQTSoft for the modem connection with the PQT/s remote will have to be selected.
76 Configuration PQTSoft Network ❑ If “Local network of instruments (RS485)” was selected 1 If the “Local network of instruments (RS485)” has been selected in the “communication parameter” setup, in addition to selecting the directory for the files to be saved, [1] the user also has to enter the number of PQT-90s present in the network (from 1 to 100) using the arrows in the numeric box named “Network number of PQT” (Number of PQTs located on the network).
78 Configuration PQTSoft Network To interrupt the automatic control mode, double click the icon present on the application bar. To activate the automatic control in a second time, press the button shown on the left. The programme will disappear from the PC screen (it will continue working in the background) and an icon will appear on the Windows application bar as shown on the previous page.
80 Configuration PQTSoft Network ❑ Define file name for downloaded data, counter and event.... 1 81 Configuration PQTSoft Network ❑ Define file name for downloaded data, counter and event... after selecting “Local network of instruments (RS485) or remote network” 4 2 3 1 2 1 1 2 5 [1] Choose the data to download from the instrument (AR1041 module) ticking the relevant check box: these data relate to the preselected variables and/or to the meters and /or events.
82 Configuration PQTSoft Network ■ Reading of instantaneous variables This function allows the reading of all the variables and meters in real time divided into two pages. PQTSoft Network Configuration 83 If you have selected “local network of instruments (RS485), it is necessary to enter the number of PQTs installed in the network (see figure on page 82) moving the arrows on the right of the number up and down.
84 Last functions PQTSoft Network ■ Configuration of analogue modem and GSM PQTSoft Network Last functions 85 ■ Contact management ❑ Selection of connections and setting of dialling properties This function allows the management of the contact list: cre- 1 Automatic configuration of analogue modem: it allows the automatic configuration of the analogue modem.
86 Last functions PQTSoft Network Last functions PQTSoft Network It is possible to enable or disable the contacts to be dialled by PQTSoft also directly on the list clicking the “Selection” column on the line corresponding to the contact to be enabled/disabled. A drop-down menu will appear: double click “On” to enable or “Off” to disable. 1 2 4 87 3 5 [1] Enter the name of the contact [2] Enter the telephone number referred to the contact.
88 Last functions PQTSoft Network [4] Specify the dialling type to be used. Choose the pulse dialling only if it is the only one available. [5] If it is selected, the phone card will be used every time the user is calling from this location (specified in the box “I am dialling from”) and with any software installed in the computer. ■ PQT-90 data conversion into Excel format This software is supplied with a converter able to convert the data file of PQT-90 into XLS (Microsoft Excel) files.