Datasheet

16 Specifications are subject to change without notice
Industrial Relay
Type RCP
Monostable
8 or 11-pin socket mounting
2 or 3 change over contacts
Long life (minimun 100.000 electrical operations)
at 10 A 250 VAC /30 VDC
Switching capacity 12 A (5x10
4
cycles)
AC coils 6 to 230 VAC
DC coils 6 to 110 VDC
Matched sockets available
Standard with LED, Push with arm and Flag
IP 40
Conform to CE low voltage directive
IMQ, UL, TÜV, CSA approved
RCP
Type
No. of pins
Contact code
Rated coil voltage
DC / AC
Product Description
Ordering Key
RCP 8 002 24 DC
Contact code
002
003
Contact rating
10 A
10 A
Contact configuration
2 change over contacts (DPDT {2-form C})
3 change over contacts (3PDT {3-form C})
Type Selection
The RCP relay can be used
for a wide range of industrial
applications.
Available in 2 or 3 change-
over contact configuration,
Octal or Undecal version.
At 20°C At 40°C
Nominal Pick-up Drop-out Pick-up Drop-out Coil
voltage voltage voltage voltage voltage resistance
VDC VDC VDC VDC VDC
6 4.8 0.6 5.2 0.6 23.5 ±10%
12 9.6 1.2 10.3 1.3 95.0 ±10%
24 19.2 2.4 20.7 2.6 430.0 ±10%
48 38.4 4.8 41.4 5.1 1630.0 ±15%
60 45.0 6.0 48.6 6.4 3000.0 ±15%
100 80.0 10.0 86.4 10.8 6800.0 ±15%
110 88.0 11.0 95.0 11.8 6800.0 ±15%
Coil Characteristics, DC
At 20°C At 40°C
Nominal Pick-up Drop-out Pick-up Drop-out Coil
voltage voltage voltage voltage voltage resistance
VAC VAC VAC VAC VAC
6 4.8 1.8 5.2 1.9 40.0 ±10%
12 9.6 3.6 10.3 3.8 160.0 ±10%
24 19.2 7.2 20.7 7.7 650.0 ±10%
48 38.4 14.4 41.4 15.5 2600.0 ±15%
115/120 88.0 36.0 95.0 38.8 11000.0 ±15%
230 176.0 72.0 190.0 77.7 11000.0 ±15%
Coil operating range: see diagram n° 1 pag. 18
Coil Characteristics, AC

Summary of content (3 pages)