Datasheet

Specifications are subject to change without notice (11.04.2016) 1
Solid state relay
Number of poles
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Connection type for control
Connection type for power
Connection configuration
Protection
Options
Product width ranging from 22.5mm to 70mm
Partial load failure detection
Zero cross switching
Ratings up to 600VACrms & 85AACrms @ 40
o
C
Up to 18000A
2
s for I
2
t and 1200Vp for blocking voltage
Control voltage range: 4 - 32 VDC
Local or remote current set-point
LED indications for the different faults
Alarm signal output for SSR or load circuit malfunction
IP20 protection
Integrated voltage transient protection with varistor
RoHS compliant
Short circuit current rating 100kArms
Product Description
Ordering Key
This slim RG design is capable
of detecting various failure
modes occuring to the heaters
and also to the product itself.
Failures which can be detected
include partial load failure,
heater loss, open circuit SSR,
short circuit SSR and SSR
over temperature. A normally
closed, potential free alarm,
opens in the event of a system
or power semiconductor fault.
A load current setpint has to be
TEACHed to the SSR either
locally by the TEACH button
on the front of the device or
remotely through the provided
terminal.
This product is available either
with integrated heatsink
(RGC1S series) and also with-
out heatsink (RGS1S series).
The minimum product width is
22.5mm. The control and aux-
iliary terminals are double box
clamps to facilitate safe loop-
ing whilst the power terminals
are either screw terminals or
box clamps depending on the
model selected.
Solid State Relays
1-Phase Integrated Heatsink
Integrated Current Monitoring
Types RGC1S
RGC 1 S 60 D 30 G K E P _
Note: Specifications stated at 25°C unless specified.
Ordering Key
1-Phase Switching Rated V, Control Rated current
1
@ 40˚C Connection Connection Connection Protection
SSR mode Blocking V* voltage I
2
t data input output configuration
RGC1: S: Zero 60:600VAC D: 4-32VDC 20: 23AAC, 525A
2
s G: Box K: Screw E: Contactor P: Over-
with heatsink cross with +10% -15%, 25: 25AAC, 1800A
2
s Clamp G: Box U: SSR temperature
current 1200Vp 26: 25AAC, 18000A
2
s Clamp protection
sensing 30: 30AAC, 1800A
2
s
31: 30AAC, 6600A
2
s
41: 43AAC, 18000A
2
s
61: 65AAC, 18000A
2
s
90: 85AAC, 18000A
2
s
* Rated voltage, Blocking voltage
1: refer to derating curves

Summary of content (22 pages)