Datasheet

Specifications are subject to change without notice (20.11.2012) 1
Solid state relay
Number of switched poles
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Connection type for control
Connection type for power
Connection configuration
External supply
Integrated fan
Monitoring features
2-pole & 3-pole AC switching solid state contactors
Product width up to 70mm
Rated operational voltage: up to 600VAC
Rated operational current: up to 75AAC
Control voltages: 5-32VDC, 20-275VAC (24-190 VDC)
Up to 15,000A²s for I²t
Motor ratings up to 11kW @ 400VAC, 25HP @ 600VAC
Integrated varistor protection on output
Optional monitoring for SSR and load malfunction
(RGC..M)
1
EMR alarm output and auxiliary output (RGC..M)
Controlled fan operation for versions with integrated fan
UL, cUL Listing
100kA Short Circuit Current Rating according to UL508
DIN or panel mount
RoHS compliant
1: RGC..M is suitable only for resistive loads
Product Description
Ordering Key
This product is intended to
replace mechanical
contactors especially when
switching is frequent. The
smallest product width in the
RGC2, RGC3 range is 54mm
(3xDIN) and goes up to
70mm.
2-pole and 3-pole switching
options are available. Switch
ON occurs at the voltage
zero cross and switch OFF
occurs at the current zero
cross. Apart from resistive
and slightly inductive loads,
the RGC is certified for motor
switching with associated
motor ratings. Varistors are
integrated for output
overvoltage protection. A
green LED gives indication of
control voltage presence.
Fan operation is controlled
for the versions which have
an integrated fan.
Detection of SSR overheat,
mains loss, SSR malfunction
and load loss is possible with
the RGC..M versions. An
EMR alarm output is
available for remote
signaling. An additional
feature with the RGC..M is
the electronic auxiliary
output. The RGC..M has
additional LEDs for load
status and alarm status
indication.
Specifications are at a
surrounding temperature of
25°C unless otherwise
specified.
Solid State Relays
3-Phase with Integrated Heatsink
Types RGC2, RGC3
Ordering Key (refer to page 2 for a vailable part nos.)
2. Refer to Current Derating curves
3. ZC= Zero Cross Switching
4. Operating voltage for RGC..M starts from 90VAC
5. AC control range for RGC..A..A.. is limited to 20-275VAC only
RGC 3 A 60 D 65 G G E D F M
SSR with Rated Control
Rated current/
Connection
Connection
Connection
External Features
heatsink voltage voltage
5
pole @4C
2
control
power
configuration supply
(Ue)
4
, (Uc) (Us)
Blocking
voltage
RGC2A: 22: D: 20: 20AAC K: Screw K: Screw E: Contactor D: 24VDC F: Integrated fan with over
2-pole switching + 42-242VAC, 5 - 32VDC 25: 25AAC G: Box Clamp G: Box Clamp A: 90-250VAC temperature protection (OTP) &
1-pole direct, ZC
3
800Vp 30: 30AAC EMR alarm output
40: 40AAC
RGC3A: 60: A: 65: 65AAC M: Monitoring for Mains loss,
3-pole switching, 42-660VAC, 20-275VAC, 75: 75AAC Load loss, SSR short circuit,
ZC 1200Vp 24-190VDC open circuit and over-
temperature with EMR alarm
output and auxiliary output
1
(suitable only for resistive loads)

Summary of content (26 pages)