E n g l i s h Flow Factor ~ 866-360-9830 INDEX FUNCTIONS MENU GETTING STARTED Initial Set-up AUTOTUNE Tune or tune at setpoint program PROPORTIONAL CYCLE-TIME Cycle-time recommendations PROGRAMMER Ramp-Soak SECOND SETPOINT (SP2) Error messages FUNCTION LIST Level 1 Level 2 Level 3 Level 4 MECHANICAL INSTALLATION DIN panel cut-out Mounting Cleaning ELECTRICAL INSTALLATION Sensor selection SPECIFICATION SAFETY AND WARRANTY INSTRUMENT PANEL FEATURES 3 4 4 4 5 5 5 5 5 6 6 7 7 7 8 9 9 9 9 9 10 11 11 12 Green
FUNCTIONS MENU ! This page can be photocopied and used as a visual aid and bookmark when working in other parts of the manual. E n g l i s h Flow Factor ~ 866-360-9830 Range of Adjustment shown under description. If applicable, factory settings shown in bold. Note: The letter K appears in the instrument display as the character K LEVL 4 LOCK PROG NO.AL DIS.S DER.S USER-PROTECTED SETTINGS u )* r d.2 ; 2i nly d.2 ;1 1i. f/s Ct3 do ;1 .2d e (rea e * .2i; .
E n g l i s h Flow Factor ~ 866-360-9830 3 Select SP1 (Main setpoint output device) GETTING STARTED After power-up the controller requires programming with the following information: Note: Dual Relay and Dual SSd Output Options Models have their outputs pre-configured. Move to Step 4. Type of Sensor (See list of temperature sensors p.11) Operating unit (See list of units p.
Hereafter in the Manual the symbol (▲▼) signifies both buttons are held pressed for 3 seconds to ENTER or EXIT Program mode. E n g l i s h Flow Factor ~ 866-360-9830 PROGRAMMER RAMP-SOAK TUNE OR TUNE AT SETPOINT PROGRAM Enter program (▲▼) and from the display tunE : oFF press and hold ✱ and press ▲ to display tunE : on or tunE : At.SP Exit program mode (▲▼). The TUNE program will now start. The display will show tunE as the process temperature climbs to setpoint.
E n g l i s h Flow Factor ~ 866-360-9830 SP2 ALARM ANNUNCIATOR SECOND SETPOINT (SP2) When an SP2 alarm mode is selected in SP2.A the alarm annunciator -AL- is displayed, alternating with the process temperature, during alarm condition. SECOND SETPOINT (SP2) Alarm Output Configure SP2 output to operate as an alarm from SP2.A in Level 2 and set the temperature alarm setting in SEt.2 Level 1. The alarm will be triggered when the process temperature changes according to the options listed below.
FUNCTION LIST (LEVELS 1 TO 4) Note: A Functions Menu is shown on page 3. LEVEL 1 PROGRAMMER SETTINGS (see page 5) [Factory settings] shown in brackets Function Options SPrr Sets the ramp rate [0] to 9995 deg/hour LEVL 1 Function SELECT AUTOTUNE tunE [oFF] E n g l i s h Flow Factor ~ 866-360-9830 Options [Factory settings] shown in brackets SPrn on [oFF] hoLd Switches the ramp on or off, or hold at last ramp value (see pages 4/5) on ParK At.
E n g l i s h Flow Factor ~ 866-360-9830 SP2 OPERATING MODES (see page 6) Function Options SP2.A [nonE] Main SP2 operating mode burn Sensor burn-out/break protection Caution: Settings affect fail safe state. [Factory settings] shown in brackets [uP.SC] dn.SC 1u.2d 1d.2u dV.hi dV.Lo bAnd FS.hi FS.Lo Cool SP2.b [nonE] LtCh hoLd nLin Subsidiary SP2 mode: latch/sequence Non-linear cool proportional band [1r.2d] 1d.2d 1r.2r 1d.2r dI.SP [1] 0.
LEVEL 4 LEVL 4 E n g l i s h Flow Factor ~ 866-360-9830 DIN PANEL CUTOUT 1/16 DIN: 45.0mm +0.6 / 0.0 wide, 45.0mm +0.6 / 0.0 high Access to level 4 is gained through UEr in level 3. Press and hold ▲ and ▼ for 10 seconds. 1/32 DIN: 45.0mm +0.6 / -0 wide, 22.2mm +0.3 / -0 high Maximum panel thickness 9.5mm Enter level 4 at Lock, release ▲ and ▼ together.
E n g l i s h Flow Factor ~ 866-360-9830 ELECTRICAL INSTALLATION EN61010 - /CSA 22.2 No 1010.1 92 (See important Safety Information page 12) Compliance shall not be impaired when fitted to the final installation. Designed to offer a minimum of Basic Insulation only. OUTPUT DEVICES Two of the following output devices are fitted to the controllers, depending on the model.
Linear process inputs mV range: SENSOR SELECTION Thermocouples tC tC tC tC tC tC tC tC tC b E J K L n r s t Description Sensor range Pt-30%Rh/Pt-6%Rh Chromel/Con Iron/Constantan Chromel/Alumel Fe/Konst NiCrosil/NiSil Pt-13%Rh/Pt Pt-10%Rh/Pt Copper/Con Resistance thermometer rtd Linearity 0 to 1800 °C 0 to 600 °C 0 to 800 °C -50 to 1200 °C 0 to 800 °C -50 to 1200 °C 0 to 1600 °C 0 to 1600 °C -200 / 250 °C 2.0 * 0.5 0.5 0.25* 0.5 0.25* 2.0* 2.0* 0.25* Pt100/RTD-2 0.
E n g l i s h Flow Factor ~ 866-360-9830 SAFETY AND WARRANTY INFORMATION INSTALLATION Designed for use: UL873 - only in products where the acceptability is determined by Underwriters Laboratories Inc. EN61010-1 / CSA 22.2 No 1010.1 - 92 To offer a minimum of Basic Insulation only. Suitable for installation within Catagory II and III and Pollution Degree 2. Copyright CARLO GAVAZZI 2000 Not to be reproduced without prior written permission from CARLO GAVAZZI.