Datasheet
Specification are subject to change without notice TCD1M DS 240714
1
Energy Management
3-phase current transformers
Type TCD1M
Product description
Group of three split-core
miniature current sensors
to be used in combination
with EM271 energy meter.
Equipped with an RJ11 wire
for a very fast installation.
The energy meter automati-
cally reads from TCD1M its
primary current rated value,
saving time for the user set-
up. It can be mounted di-
rectly on the cables whose
current is to be monitored,
without need to interrupt the
load power supply.
•3-phasecurrenttransformersetcompatible
toEM271energymeter
•Primarycurrent100A
•Holesize15.7mm
•Auto-detectionoftheprimarycurrentratedvalueby
theEM271energymeter
•Forcablemounting
•UmbilicalconnectiontoEM271energymeterthrough
RJ11
How to order
TCD1M 100 80CM X
Model
Primarycurrent
Cablelenght
Option
Type Selection
Primarycurrent
100: 100A primary current input
Cablelength(RJ11side)
80CM: 80cm
Option
X: none
Specification
Electricalspecifications
Rated Primary Current
45/65Hz 100A (1-120)
Current (continuos) 300A max
Winding DC resistance at 20°C 384Ω max
Secondary Output at
Accuracy 1%
Linearity 0.5%
Phase error at rated
current range ≤2°
Operating temperature range -40°C to +65°C (-40°F
to149°F) (R.H. < 90% non-
condensing @ 40°C)
Storage temperature range -40°C to +65°C (-40°F
to149°F) (R.H. < 90% non-
condensing @ 40°C)
Dieletric withstand voltage
(Hi-pot) 2500V/1mA/1min
Impulse withstand voltage 5kV Peak
Insulation Resistance DC500V/100MΩ min
Max primary cable system
voltage 660V
Mechanicalspecification
Current transformer terminal 150cm (UL1015 22AWG
PVC wire, 0.20mm
2
)
Current transformer housing P6331
Opening Angle 180 degree
Approx weight 290g
Approvals CE
Mounting Cable Mounting
Connections RJ11
Protection Degree IP20
Hole Size Max 15.7mm