Product Brochure

66
www.carlon.com
(C) Tap Conductors. Tap conductors of a type suitable
for the temperature encountered shall be permitted
to run from the luminaire (fixture) terminal connection
to an outlet box placed at least 300 mm (1 ft.) from
the fixture. Such tap conductors shall be in suitable
raceway or Type AC or MC cable of at least 450 mm
(18 in.) but not more than 1.8 m (6 ft) in length.
Article 504
504.20 Wiring Methods. Intrinsically safe apparatus and
wiring shall be permitted to be installed using any of the
wiring methods suitable for unclassified locations, including
Chapter 7 and Chapter 8. Sealing shall be as provided in
Section 504.70, and separation shall be as provided in
Section 504.30.
Article 505
505.15 Wiring Methods.
Wiring methods shall maintain
the integrity of protection techniques and shall comply with
505.15(A), (B), or (C).
(A) Class I, Zone 0. In Class I, Zone 0 locations, only
intrinsically safe wiring methods in accordance with
Article 504 shall be permitted
.
FPN: Article 504 only includes protection technique “ia.”
Article 551 – Recreational Vehicles and
Recreational Vehicle Parks
551.47 Wiring Methods.
(G) Protected. Metal-clad, Type AC, or nonmetallic-
sheathed cables and electrical nonmetallic tubing
shall be permitted to pass through the centers of the
wide side of 2 4 wood studs. However, they shall
be protected where they pass through 2 2 wood
studs or at other wood studs or frames where the
cable or tubing would be less than 32 mm (1
1
4 in.)
from the inside or outside surface. Steel plates on
each side of the cable or tubing, or a steel tube, with
not less than 1.35 mm (0.053 in.) wall thickness, shall
be installed to protect the cable or tubing. These
plates or tubes shall be securely held in place. Where
nonmetallic-sheathed cables pass through punched,
cut, or drilled slots or holes in metal members, the
cable shall be protected by bushings or grommets
securely fastened in the opening prior to installation
of the cable.