Product Brochure

23
www.carlon.com
Section 4
Masonry Construction
Reference NEC Section 362.10 Uses Permitted:
The use of electrical nonmetallic tubing and fittings shall be
permitted:
(1) In any building not exceeding three floors above grade
a. For exposed work, where not prohibited by 362.12(10)
b. Concealed within walls, floors, and ceilings.
(2) In any building exceeding three floors above grade,
ENT shall be concealed within walls, floors, and ceilings
where the walls, floors, and ceilings provide a thermal
barrier of material that has at least a 15 minute finish
rating as identified in listings of fire-rated assemblies.
(see Section 3, Table 3-1 in this manual). The 15-minute-
finish-rated thermal barrier shall be permitted to be
used for combustible or noncombustible walls, floors,
and ceilings.
Exception: Where a fire sprinkler system(s) is installed in
accordance with NFPA 13-1999, Standard for the Installation
of Sprinkler Systems, on all floors, ENT is permitted to be
used within walls, floors, and ceilings, exposed or concealed,
in buildings exceeding three floors above grade.
Questions About ENT
1. CAN I USE CARLON ENT IN BLOCK WALL?
Yes. The installation of ENT in block walls requires less
lifting of blocks by the mason. The pliable construction of
ENT allows for bending and threading through the block
cavity at a convenient work height.
2. WHAT ARE THE ADVANTAGES OF USING RIGID
CONDUIT VS. ENT IN A MASONRY WALL?
There are none. Read on:
a. If the receptacles are fed from overhead it provides a
length of conduit from the roughed-in receptacle to