Product Brochure

58
www.carlon.com
Article 314 — Outlet, Device, Pull, and Junction
Boxes; Conduit Bodies; Fittings; and Manholes
I. SCOPE AND GENERAL
314.1 Scope. This article covers the installation and use of
all boxes and conduit bodies used as outlet, device, junction,
or pull boxes, depending on their use, and manholes and
other electric enclosures intended for personnel entry. Cast,
sheet metal, nonmetallic, and other boxes such as FS, FD,
and larger boxes are not classified as conduit bodies. This
article also includes installation requirements for fittings
used to join raceways and to connect raceways and cables
to boxes and conduit bodies.
314.2 Round Boxes. Round boxes shall not be used
where conduits or connectors requiring the use of lock nuts
or bushings are to be connected to the side of the box.
314.3 Nonmetallic Boxes.
Nonmetallic boxes shall be
permitted only with open wiring on insulators, concealed
knob-and-tube wiring, cabled wiring methods with entirely
nonmetallic sheaths, flexible cords, and nonmetallic raceways.
Exception No. 1: Where internal bonding means are provided
between all entries, nonmetallic boxes shall be permitted to
be used with metal raceways or metal-armored cables.
Exception No. 2: Where integral bonding means with a
provision for attaching an equipment bonding jumper inside
the box are provided between all threaded entries in non-
metallic boxes listed for the purpose, nonmetallic boxes shall
be permitted to be used with metal raceways or metal-
armored cables.
314.4 Metal Boxes. All metal boxes shall be grounded in
accordance with the provisions of Article 250.
314.17 Conductors Entering Boxes, Conduit
Bodies, or Fittings. Conductors entering boxes, conduit
bodies, or fittings shall be protected from abrasion and shall
comply with 314.17(A) through (D).
(A) Openings to Be Closed. Openings through which
conductors enter shall be adequately closed.
(B) Metal Boxes and Conduit Bodies. Where metal
boxes or conduit bodies are installed with open wiring
or concealed knob-and-tube wiring, conductors shall
enter through insulating bushings or, in dry locations,
through flexible tubing extending from the last
insulating support to not less than 6 mm (
1
/4 in.)