Product Brochure

25
www.carlon.com
Section 5
Exposed Construction
Reference NEC Section 362.10: The use of electrical
nonmetallic tubing and fittings shall be permitted:
(1) In any building not exceeding three floors above grade.
a. For exposed work, where not prohibited by 362.12(10).
b. Concealed within walls, floors, and ceilings.
(2) In any building exceeding three floors above grade,
ENT shall be concealed within walls, floors, and ceilings
where the walls, floors, and ceilings provide a thermal
barrier of material that has at least a 15-minute finish
rating as identified in listings of fire-rated assemblies.
The 15-minute-finish-rated thermal barrier shall be
permitted to be used for combustible or noncombustible
walls, floors, and ceilings.
Questions About ENT
1. WHAT DOES “NOT SUBJECT TO PHYSICAL
DAMAGE” MEAN?
It means the normal activity in the area where the
installation is located is such that it would not damage
the installation. In locations where ENT would be exposed
to physical damage, guards must be installed to provide
protection and be arranged to prevent such damage.
2. WHERE CAN I RUN ENT EXPOSED?
You can run ENT exposed in commercial buildings, ware-
houses, self storage buildings, condominiums, apartments,
hotel/motel complexes, schools, and other structures
where the building is not over three floors above grade.
3. EXACTLY WHAT IS EXPOSED CONSTRUCTION?
Exposed construction is where you can see the ENT and
boxes when construction is complete, i.e., attic crawl spaces
where ENT is fastened to studs, and in warehouses where
ENT is fastened to steel trusses to feed hi-bay fixtures.
4.
ARE THERE ANY SPECIAL REQUIREMENTS WHEN
RUNNING FROM A PANEL INTO A FREEZER?
Yes. The conduit must be sealed to prevent air circulation
(see NEC Article 300.7, Section 10 of this manual.)