(C) Floor Boxes. Boxes listed specifically for this
application shall be used for receptacles located in
the floor.
Exception: Where the authority having jurisdiction judges
them free from likely exposure to physical damage,
moisture, and dirt, boxes located in elevated floors of
show windows and similar locations shall be permitted
to be other than those listed for floor applications.
Receptacles and covers shall be listed as an assembly
for this type of location.
(D) Boxes at Ceiling-Suspended (Paddle) Fan Outlets.
Where a box is used as the sole support of a ceiling-
suspended (paddle) fan, the box shall be listed for
the application and for the weight of the fan to be
supported. The installation shall comply with 422.18.
314.43 Nonmetallic Boxes.
Provisions for supports or other mounting means for
nonmetallic boxes shall be outside of the box, or the box
shall be constructed so as to prevent contact between the
conductors in the box and the supporting screws.
Article 410
410.14 Connection of Electric-Discharge
Luminaires (Lighting Fixtures).
(A) Independent of the Outlet Box. Electric-discharge
luminaires (lighting fixtures) supported independent
of the outlet box shall be connected to the branch
circuit through metal raceway, nonmetallic raceway,
Type MC cable, Type AC cable, Type MI cable, non-
metallic sheathed cable, or by flexible cord as permit-
ted in 410.30(B) or (C).
(B) Access to Boxes. Electric-discharge luminaires
(lighting fixtures)
surface mounted over concealed
outlet, pull, or junction
boxes shall be installed with
suitable openings in back of the fixture to provide
access to the boxes.
410.67 Wiring.
(A) General. Conductors that have insulation suitable for
the temperature encountered shall be used.
(B) Circuit Conductors. Branch-circuit conductors that
have an insulation suitable for the temperature
encountered shall be permitted to terminate in the
luminaire (fixture).