Product Brochure

28
www.carlon.com
Section 6
Above a suspended ceiling
Reference NEC Section 362.10(5) Permitted Uses:
(5)
Above suspended ceilings where the suspended ceilings
provide a thermal barrier of material that has at least a 15
minute finish rating as identified in listings of fire-rated
assemblies, except as permitted in Section 362.10(1)(a).
Exception: Where a fire sprinkler system(s) is installed in
accordance with NFPA 13-1999, Standard for the Installation
of Sprinkler Systems, on all floors, ENT is permitted to be
used within walls, floors, and ceilings, exposed or concealed,
in buildings exceeding three floors above grade.
Questions About ENT
1. CAN I USE ENT FOR FIXTURE TAILS?
It depends. If the ENT fixture tail is used in non-air-handling
plenum, it is permitted (see NEC Section 410.14 and
410.67(C). If the ENT would be used as a fixture tail in an
air-handling plenum, the answer is NO. (ref. NEC Section
300.22). See illustration 6-1 and 6-2 in this section.
2. CAN I USE ENT FOR BRANCH LIGHTING AND
POWER CIRCUITS RUN ABOVE A SUSPENDED
CEILING?
Yes, provided the area, above the lay-in ceiling, is not
used as an air-handling space.
3. WHAT IF THE INSPECTOR SAYS THAT THE CEIL-
ING INSTALLATION IS EXPOSED AND IS NOT
ALLOWED?
This is not an exposed condition. Refer to the NEC Article
100 – Definitions – Accessible: Capable of being removed
or exposed without damaging the building structure or
finish, or not being permanently closed by the structure
or finish of the building.
4.
I AM INSTALLING ENT IN A NON-AIR-HANDLING
PLENUM. THE ENT WILL BE SUPPORTED ON
WOODEN JOISTS. WHERE DO I INSTALL THE
ENT ON THE JOIST?
Refer to Section 3 of this manual (questions 2, 3
and 4).
It refers to the hole locations in the joist or running
parallel with the joist.