Product Brochure

31
www.carlon.com
Section 7
Boxes and Supports
Reference NEC Article 314 Outlet, Device, Pull and Junction
Boxes, Conduit Bodies, Fittings, and Manholes.
314.1. Scope. This article covers the installation and use of
all boxes and conduit bodies used as outlet, junction, or pull
boxes, depending on their use, and manholes and other
electric enclosures intended for personnel entry. Cast, sheet
metal, nonmetallic, and other boxes such as FS, FD, and
larger boxes are not classified as conduit bodies. This article
also includes installation requirements for fittings used to
join raceways and to connect raceways and cables to boxes
and conduit bodies.
314.3. Nonmetallic Boxes. Nonmetallic boxes shall be per-
mitted only with open wiring on insulators, concealed knob-
and-tube wiring, cabled wiring methods with entirely non-
metallic sheaths, flexible cords, and nonmetallic raceways.
Questions about ENT
1. CAN I SUPPORT A 20 POUND FIXTURE FROM A
CARLON
NONMETALLIC CEILING BOX THAT IS
FIRMLY SUPPORTED
FROM THE STRUCTURE?
Yes. See NEC Sections 314.33 and 314.27. Maximum
fixture weight for a Carlon ceiling box listed for fixture
support is 50 pounds.
2.
WHAT SPECIAL REQUIREMENTS MUST I ADHERE
TO FOR THE INSTALLATION OF A CARLON NON-
METALLIC BOX IN A FIRE RESISTIVE WALL?
a. Precautions must be taken to assure that the wall
openings are not oversized. The clearance between the
edge of the box and the wall should not exceed
1
/8 inch
(see NEC Section 314.20).
b. If nonmetallic boxes are installed on opposite sides
of the fire resistive wall assembly without the use of
mineral wool batt insulation, must be separated by a
horizontal distance of 24 inches. Mineral wool batt can
also be used to achieve a 7 inch separation. Putty pads