Product Brochure
68
www.carlon.com
system shall be so arranged, with approved smoke
detection devices, that upon the detection of fire or
products of combustion in the underfloor space the
circulation of air will cease.
(4) Openings in raised floors for cables protect cables
against abrasions and minimize the entrance of
debris beneath the floor.
(5) Cables, other than those covered in (2) and those
complying with (a), (b), and (c), shall be listed as
Type DP cable having adequate fire-resistant char-
acteristics suitable for use under raised floors of an
information technology equipment room.
(a) Interconnecting cables enclosed in a raceway.
(b) Interconnecting cables listed with equipment
manufactured prior to July 1, 1994, being
installed with that equipment.
(c) Cable type designations Type TC (Article 336);
Types CL2, CL3, and PLTC (Article 725); Type
ITC (Article 727), Types NPLF and FPL (Article
760); Types OFC and OFN (Article 770); Types
CM and MP (Article 800); and Type CATV
(Article 820). These designations shall be
permitted to have an additional letter P or R or
G. Green, with one or more yellow stripes,
insulated single conductor cables, 4 AWG and
larger, marked “for use in cable trays” or “for
CT use” shall be permitted for equipment
grounding.
FPN: One method of defining fire resistance is by
establishing that the cables do not spread fire to
the top of the tray in the “Vertical Tray Flame
Test” referenced in ANSI/UL 1581-1991, Standard
for Electrical Wires, Cables, and Flexible Cords.
Another method of defining fire resistance is for
the damage (char length) not to exceed 1.5 m
(4 ft. 11 in.) when performing the CSA “Vertical
Flame Test – Cables in Cable Trays,” as described in
CSA C22.2 No. 0.3-M-1985, Test Methods for
Electrical Wires and Cables.
(6) Abandoned cables shall not be permitted to remain
unless contained in metal raceways.