ENT Specifications
GUIDE SPECIFICATION FOR ENT
• Electrical Nonmetallic Tubing (ENT) is designed to replace
EMT, flexible metal conduit or other raceway systems in
accordance with Article 362 of the National Electrical
Code, other applicable sections of the Code and local
codes.
Any ENT used shall be listed to the requirements of UL
1653 and meets NEMA TC-13.
• ENT shall be recognized by The National Evaluation
Service, Inc. for use in fire resistive construction.
• Penetration of fire rated walls, floors or ceilings shall use
classified Through-Penetration Firestop Systems described
in the current Underwriters Laboratories Fire Resistance
Directory.
• Fittings and outlet boxes shall be designed for use with
ENT and listed by Underwriters Laboratories. All fittings,
boxes and accessories shall be manufactured by CARLON.
• Only CARLON ENT Blue cement recommended specifically
for use with ENT and PVC Schedule 40 fittings shall be used.
• Unless indicated differently on drawings, ENT systems
shall be color coded: BLUE,YELLOW, or RED. ENT can be
used for identifications.
FEATURES
• UL Listed, Trade Sizes (
1
/
2" to 2")
• UL recognizes the use of PVC Schedule 40 cement type
fittings with all sizes of ENT
• ENT ambient temperature range -4˚F (installation to 122˚F)
• ENT rated for 90˚C conductors
• One piece ENT Coupling, Threaded Terminator and
Schedule 40 Transition Fitting are rated concrete tight
without tape by UL Recognized in current NEC ref. Article
362
• Recognized for use in 2-hour fire resistive nonload bearing
and load bearing wall assemblies per NER-290 and ER-
5644