Product Brochure

www.carlon.com
15
Technical Information
UL recognizes the use of PVC RNC cement type fittings with all sizes of ENT
ENT rated for 90 deg C conductors
One piece ENT Coupling, Threaded Terminator and RNC Transition Fitting are rated concrete tight
without tape by UL
Recognized for use in 2-hour fire resistive nonload bearing and load bearing wall assemblies
Recognized for use in 1-hour fire resistive nonload bearing wall assemblies
Recognized for use in a fire resistive ceiling assembly (up to 3 hours)
Recognized for Through-Penetration Firestop systems as classified by UL to meet BOCA, SBCCI and ICBO codes.
Conductors easily push through the raceway (up to approximately 50 feet)*
For use in buildings in accordance with NEC Article 362
Approved for installations of a one and two hour fire rated wall assembly and up to a three hour rated
floor/ceiling assembly
Outside Diameters meet IPS Dimensions
Storage -4°F to 158°F
Handling -4°F to 104°F
Features
Approved Uses:
Typical Applications:
Concrete slab – NEC Article 362
Walls - wood stud, masonry and metal stud – NEC Article 362.
Ceilings - permanent or dropped (free air only) – NEC Article 362.
Exposed – NEC Article 362
Public Assembly – NEC Section 518.4, in nonfire rated and certain five rated structures
Prewired – NEC Article 362
Classified by UL 1479 for Through Penetration Firestop Systems in UL Guide Category XHEZ and current
UL Fire Resistance Directory
Three hour rated floor/ceiling assemble
Raised Floors – NEC Section 645.5(D)(2)
Exposed or concealed in building above three floors when a fire sprinkler system is installed in accordance with
NFPA 13 – NEC Section 362.10(2)
For use in residential attics up to 3 feet above the bottom of the ceiling joist.
Residential: Low or high rise – multi or single family
Commercial: Low or high rise – office, retail, hotel/motel, restaurant, etc.
Nursing Homes/Hospitals in nonpatient care areas only
Schools, classrooms, dormitories, offices
Fire Alarm Systems
Recreational vehicles and parks
Solar Photovoltaic systems
Marinas and boatyards
Other uses per the current NEC