Cut Sheet
www.carlon.com
15
Technical Information
• Recognized for use with PVC rigid nonmetallic conduit fittings with all sizes of ENT
• ENT rated for 90°C conductors US, and 75°C Canada
• One piece ENT Coupling, Threaded Terminator and RNC Transition Fitting are rated concrete tight
without tape
• Recognized for use in 2-hour fire resistive nonload bearing and load bearing wall assemblies
• Recognized for use in 1-hour fire resistive nonload bearing wall assemblies
• Recognized for use in a fire resistive ceiling assembly (up to 3 hours)
• Recognized for Through-Penetration Firestop systems as classified by UL to meet ICC building codes.
• Conductors easily push through the raceway (up to approximately 50 feet)*
• For use in buildings in accordance with NEC Article 362 / CEC Section 12-1500
• Outside Diameters meet IPS Dimensions
• Storage -4°F to 158°F
• Handling -4°F to 104°F
Features
Approved Uses:
Typical Applications:
• Concrete slab – NEC Article 362 / CEC Section 12-1500
• Walls - wood stud, masonry and metal stud – NEC Article 362 / CEC Section 12-1500
• Ceilings - permanent or dropped (free air only) – NEC Article 362 / CEC Section 12-1500
• Exposed – NEC Article 362 / CEC Section 12-1500
• Public Assembly – NEC Section 518.4, in nonfire rated and certain five rated structures
• Prewired – NEC Article 362 / CEC Section 12-1500
• Classified by UL 1479 for Through Penetration Firestop Systems in UL Guide Category XHEZ and current
UL Fire Resistance Directory
• Three hour rated floor/ceiling assemble
• Raised Floors – NEC Section 645.5(D)(2)
• Exposed or concealed in building above three floors when a fire sprinkler system is installed in accordance with
NFPA 13 – NEC Section 362.10(2)
• For use in residential attics up to 3 feet above the bottom of the ceiling joist.
• Maximum ambient temperature 140°F (60°C)
• Residential: Low or high rise – multi or single family
• Commercial: Low or high rise – office, retail, hotel/motel, restaurant, etc.
• Nursing Homes/Hospitals in nonpatient care areas only
• Schools, classrooms, dormitories, offices
• Fire Alarm Systems
• Recreational vehicles and parks
• Solar Photovoltaic systems
• Marinas and boatyards
• Other uses per the current NEC and CEC