Technical Information
Recognized for use with PVC rigid nonmetallic conduit fittings with all sizes of ENT
ENT rated for 90°C conductors US, and 75°C Canada
One piece ENT Coupling, Threaded Terminator and RNC Transition Fitting are rated concrete tight
without tape
Recognized for use in 2-hour fire resistive nonload bearing and load bearing wall assemblies
Recognized for use in 1-hour fire resistive nonload bearing wall assemblies
Recognized for use in a fire resistive ceiling assembly (up to 3 hours)
Recognized for Through-Penetration Firestop systems as classified by UL to meet ICC building codes.
Conductors easily push through the raceway (up to approximately 50 feet)*
For use in buildings in accordance with NEC Article 362 / CEC Section 12-1500
Outside Diameters meet IPS Dimensions
Storage -4°F to 158°F
Handling -4°F to 104°F
Features
Approved Uses:
Typical Applications:
Concrete slab – NEC Article 362 / CEC Section 12-1500
Walls - wood stud, masonry and metal stud – NEC Article 362 / CEC Section 12-1500
Ceilings - permanent or dropped (free air only) – NEC Article 362 / CEC Section 12-1500
Exposed – NEC Article 362 / CEC Section 12-1500
Public Assembly – NEC Section 518.4, in nonfire rated and certain five rated structures
Prewired – NEC Article 362 / CEC Section 12-1500
Classified by UL 1479 for Through Penetration Firestop Systems in UL Guide Category XHEZ and current
UL Fire Resistance Directory
Three hour rated floor/ceiling assemble
Raised Floors – NEC Section 645.5(D)(2)
Exposed or concealed in building above three floors when a fire sprinkler system is installed in accordance with
NFPA 13 – NEC Section 362.10(2)
For use in residential attics up to 3 feet above the bottom of the ceiling joist.
Maximum ambient temperature 140°F (60°C)
Residential: Low or high rise – multi or single family
Commercial: Low or high rise – office, retail, hotel/motel, restaurant, etc.
Nursing Homes/Hospitals in nonpatient care areas only
Schools, classrooms, dormitories, offices
Fire Alarm Systems
Recreational vehicles and parks
Solar Photovoltaic systems
Marinas and boatyards
Other uses per the current NEC and CEC