In this section... Carlon PVC Elbows, Conduit & Fittings ® Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories................................E-454–E-481 Conduit Bodies (for use with Schedule 40 and 80 Conduit)...........................................................E-482–E-487 Switch and Junction Boxes..........................................E-488–E-492 Straps, Clamps and Accessories..................................E-493–E-496 Spacers.................................................
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories A job that normally takes 20 minutes — DONE in two minutes or less! Carlon PVC Conduit Repair System ® The new, revolutionary design Carlon® PVC Conduit Repair System significantly reduces the time and money associated with repairing broken PVC conduits, a.k.a. “stub-ups”, in concrete slabs.
Elbows, Sweeps and Accessories 1 2 Cut broken conduit off flush. Insert plug to keep conduit clean/dry through balance of rough-in. Once rough-in is complete, remove plug and continue with Step 3. 4 The guide will direct the cutter; the stop will touch when completed. 5 I nsert the coupling and cement into place using the cement manufacturer’s instructions. Cementing Instructions: A. C lean socket I.D. and spigot O.D. of dirt and moisture. B.
E23018 90° R 45° ELBOW R 45° 30° ELBOW R 30° 221⁄2° ELBOW R 22.5° BELLED END CAT. NO. UA9AD UA9ADR-CAR UA9AE UA9AFR-CTN UA9AG UA9AH UA9AJ UA9AK-CAR UA9AL UA9AM UA9AN UA9AP UA9AR UA7AD UA7AE UA7AF UA7AF-CAR UA7AG UA7AH UA7AJ UA7AJ-CAR UA7AK UA7AL UA7AM UA7AN UA7AP UA7AR UA6AD UA6AE UA6AF UA6AG UA6AH UA6AJ UA6AK UA6AL UA6AM UA6AN UA6AP UA6AR UA5AD UA5AE UA5AF UA5AG UA5AH UA5AJ UA5AK UA5AL UA5AM UA5AN UA5AP UA5AR CAT. NO.
SEGMENT 90° ELBOW 90° R PLAIN END BELLED END CAT. NO. UA9CF UA9DF UA9EF UA9FF UA9HF UA9CG UA9DG UA9EG UA9FG UA9HG UA9CH UA9DH UA9EH UA9FH UA9HH UA9CJ UA9DJ UA9EJ UA9FJ-UPC UA9HJ UA9JJ UA9CK UA9DK UA9EK UA9FK-UPC UA9HK UA9CL UA9DL UA9EL UA9FL UA9HL UA9IL UA9DM UA9EM UA9FM UA9HM — UA9DN UA9EN UA9FN UA9HN UA9IN UA9JN UA9EP UA9FP UA9HP UA9IP UA9FR UA9HR UA9IR — UA9HT* CAT. NO.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories Schedule 40 Elbows — Special Radius (continued) E23018 PLAIN END BELLED END SEGMENT CAT. NO. 30° ELBOW UA6CJ UA6DJ UA6FJ UA6HJ UA6CK UA6DK UA6CL UA6DL UA6FL UA6HL UA6DM UA6FM UA6HM UA6DN UA6FN UA6HN UA6FP UA6HP UA6FR UA6HR UA3DJ UA3FJ UA3HJ UA3HK UA3DL UA3FL UA3HL UA3DM UA3HM UA3DN UA3FN — UA3HN UA3FP UA3HP — UA3FR UA3HR UA3FT* R 30° 111⁄4° ELBOW 11.25° R CAT. NO. NOM. DIAM. (IN.
Standard Radius ITEM 90° ELBOW 90° R 45° ELBOW R 45° 30° ELBOW R 30° 221⁄2° ELBOW PLAIN END BELLED END CAT. NO. CAT. NO. UB9AD — UB9AE — UB9AF — UB9AG — UB9AH — UB9AJ — UB9AK — UB9AL — UB9AN — UB9AP UB9APB UB9AR — UB7AD — UB7AE-UPC — UB7AF-UPC — UB7AG — UB7AH — UB7AH— CAR UB7AJ-UPC — UB7AK — UB7AL — UB7AN — UB7AP UB7APB UB7AR — UB6AD — UB6AE — UB6AF — UB6AG — UB6AH — UB6AJ — UB6AK — UB6AL — UB6AN — UB6AP — UB6AR — UB5AL — UB5AN — UB5AP UB5APB SIZE (IN.) PLAIN END STD. CTN. BELLED END STD.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories Schedule 80 Elbows — Flexible PVC Elbows Special Radius (continued) PLAIN END BELLED END SEGMENT CAT. NO. 45° ELBOW R 45° 30° ELBOW RADIUS (IN.) PLAIN END STD. CTN. BELLED END STD. CTN.
Elbows, Sweeps and Accessories BELLED END ITEM CAT. NO. 90° ELBOW UA9ADCB-CTN UA9AECB-CTN UA9AFCB-CTN UA9AGCB-UPC UA9AHCB-UPC UA9AJCB-UPC UA9AKCB-CTN UA9ALCB-UPC UA9AMCB UA9ANCB UA9APCB UA9ARCB UA7AGCB UA7AHCB UA7AJCB UA7AKCB UA7ALCB UA7AMCB UA7ANCB UA7APCB UA7ARCB UA6AJCB UA6ANCB UA6ARCB 90° R 45° ELBOW R 45° 30° ELBOW BELLED END SIZE (IN.) STD. CTN.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories Deep-Socket Schedule 40 Utility Elbows with Integral Belled Ends Long-Belled Utility Elbows Non-UL Listed SEGMENT CAT. NO. NOM. DIA. (IN.) RADIUS (IN.) STD. CTN. STD. WT. (LBS.
Elbows, Sweeps and Accessories SEGMENT CAT. NO. 90° SWEEP — 48" RADIUS PE9HN PE9HP SIZE (IN.) STD. CTN. 4 5 1 1 SEGMENT CAT. NO. 111⁄4° SWEEP — 150" RADIUS PE3SP Segmented Sweeps PE3SNS PE3SPS PE3SRS 11.25° R 90° R SEGMENT CAT. NO. 45° SWEEP — 150" RADIUS PE7SP SIZE (IN.) STD. CTN. 5 1 SIZE (IN.) STD. CTN. 5 1 4 5 6 1 1 1 Note: Consult your Thomas & Betts Sales Team for additional sizes R 45° P&C Duct DB-60 Sweeps SEGMENT 90° SWEEP 90° R CAT. NO.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories P&C Duct DB-60 Sweeps (continued) SEGMENT CAT. NO. 30° SWEEP PF6CJ PF6CL PF6DL PF6DN PF6DP PF6CH PF6FJ PF6FL PF6FN PF6FR PF6HJ PF6HN PF6HP PF6HR PF6IN PF6IP PF6SJ PF6SN PF6SP PF6VJ PF6VN PF6VR PH5DL PF5DN PF5DP PF5FF PF5FL PF5FN PF5FP PF5FR PF5HL PF5HN PF5HR PF5IJ PF5IL PF5IP PF5IR PF5SL PF5SN PF5SP PF5SR PF5VN PF5VP PF5VR R 30° 221⁄2° SWEEP R 22.5° SIZE (IN.) RADIUS (IN.) STD. CTN.
Elbows, Sweeps and Accessories SEGMENT CAT. NO. 90° SWEEP PH9CJ PH9CL PH9CN PH9DJ PH9DL PH9DN PH9DP PH9FJ PH9FL PH9FN PH9FP PH9FR PH9HJ PH9HL PH9HN PH9HP PH9HR PH9IJ PH9IL PH9IN PH9IR PH9OJ PH9SJ PH9SL PH9SN PH9SP PH9SR PH9VN PH9VP PH9VR 90° R Note: Consult your Thomas & Betts Sales Team for additional sizes SIZE (IN.) RADIUS (IN.) STD. CTN.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories P&C Duct DB-60 Sweeps (continued) SEGMENT CAT. NO. 30° SWEEP PF6CJ PF6CL PF6DL PF6DN PF6DP PF6CH PF6FJ PF6FL PF6FN PF6FR PF6HJ PF6HN PF6HP PF6HR PF6IN PF6IP PF6SJ PF6SN PF6SP PF6VJ PF6VN PF6VR PH5DL PF5DN PF5DP PF5FF PF5FL PF5FN PF5FP PF5FR PF5HL PF5HN PF5HR PF5IJ PF5IL PF5IP PF5IR PF5SL PF5SN PF5SP PF5SR PF5VN PF5VP PF5VR R 30° 221⁄2° SWEEP R 22.5° SIZE (IN.) RADIUS (IN.) STD. CTN.
Elbows, Sweeps and Accessories SEGMENT CAT. NO. 90° SWEEP PH9CJ PH9CL PH9CN PH9DJ PH9DL PH9DN PH9DP PH9FJ PH9FL PH9FN PH9FP PH9FR PH9HJ PH9HL PH9HN PH9HP PH9HR PH9IJ PH9IL PH9IN PH9IR PH9OJ PH9SJ PH9SL PH9SN PH9SP PH9SR PH9VN PH9VP PH9VR 90° R Note: Consult your Thomas & Betts Sales Team for additional sizes SIZE (IN.) RADIUS (IN.) STD. CTN.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories P&C Duct Adapters P&C Duct End Bells Male Adapter End Bell CAT. NO. SIZE (IN.) STD. CTN. E943F E943H E943J E943L E943N E943P E943R 1 11⁄2 2 3 4 5 6 50 25 50 50 20 5 10 CAT. NO. SIZE (IN.) STD. CTN. E942F E942H E942J E942L E942N E942P E942R 1 11⁄2 2 3 4 5 6 50 25 30 25 15 8 6 Female Adapter CAT. NO. SIZE (IN.) STD. CTN.
Elbows, Sweeps and Accessories SEGMENT CAT. NO. SIZE (IN.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories P&C Duct Canadian DB/2 Duct Fittings PVC 5° Coupling B x B — Solvent Weld P&C Duct End Bell (For use with DB/2 Duct only) CAT. NO. SIZE (IN.) STD. CTN. CAT. NO. SIZE (IN.) STD. CTN. CE245J CE245L CE245N CE245P 2 3 4 5 30 15 10 20 CE297J CE297L CE297N CE297P 2 3 4 5 40 50 30 15 PE 5° Coupling — Push Fit CAT. NO. SIZE (IN.) STD. CTN.
Elbows, Sweeps and Accessories SEGMENT 30° SWEEP R 30° • Straight-end length 3" SEGMENT 90° SWEEP CAT. NO. BEND RADIUS STD. CTN.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories Telephone Duct Couplings Telephone Duct End Bells Sleeve Coupling CAT. NO. Square to Round SIZE (IN.) For Repair Work E900N 4x6 E900NU 4 x 12 E900NW (WHITE) 4x6 Split-Sleeve Couplings E900NS 4 E900NS8 (WHITE) 4x8 E900NSW (WHITE) 4 E900PS 5 For Type D Duct Applications Only E900DN (WHITE) 4 STD. CTN. E903N 25 10 25 Internal Stop E908N E914N 4 (Sq.) 4 Molded End Bell 25 15 25 15 CAT. NO. E971N SIZE (IN.
Elbows, Sweeps and Accessories Adapts telephone duct to fiber transite MCD Internal Adapter CAT. NO. E901N Split E901NS SIZE (IN.) STD. CTN. 4 24 4 24 Adapts Telephone Duct to P&C Duct and Rigid Non-Metallic Conduit P&C Duct Adapter CAT. NO. E913N E913NF SIZE (IN.) STD. CTN. 4 4 15 15 Adapts Threaded Metal Pipe to Telephone Duct Female Adapter CAT. NO. E902N SIZE (IN.) STD. CTN.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories Split Sleeve Coupling CAT. NO. Schedule 40 and 80 E200JS6 E200KS7 E200LS7 E200LSS* E200MS8 E200NS8 E200NSS* E200PS8 E200PS9 E200RS1 C Duct E900NS8 (WHITE) E900NSW (WHITE) SIZE IN. DESCRIPTION LENGTH IN. SPLIT STD. CTN. STD. WT. (LBS.
Multi-Purpose Spray-On Low-VOC PVC Cements Applications: • Equivalent to a medium-bodied low-VOC, quick-setting clear cement • For use up to 4" diameter Schedule 40 or 80 PVC electrical conduit • No more spills • Reuse can until empty • For use with PVC raceways only. Not recommended for use on water, sewer, natural gas, compressed gas or air connections • Installation: 50° to 80° F; Storage: 35° to 120° F • Meets ASTM D-2564 • Three-year shelf life • One 4-oz. can is equivalent to 4 oz.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories RECOMMENDED PIPE VISCOSITY AT 75° F APPLICATION AND SIZES SET-UP TIME (EVAPORATION RATE) RECOMMENDED INSTALLATION TEMP. LAP SHEAR @ 73° F VISCOSITY AT 75° F AS MANUFACTURED Recommended for all grades and types of Carlon ® wireway and fittings, except Flex-Plus® Blue™ ENT (Electrical Non-Metallic Tubing). 10°–30° F 30°–50° F 50°–70° F 70°–90° F 40° to 100° F 2 hrs. 350 psi 16 hrs. 800 psi 72 hrs.
Elbows, Sweeps and Accessories Recommended for all grades and types of Carlon ® wireway and fittings, except Flex-Plus® Blue™ ENT (Electrical Non-Metallic Tubing). Up through 6" diameter. SET-UP TIME (EVAPORATION RATE) RECOMMENDED INSTALLATION TEMP. LAP SHEAR @ 73° F VISCOSITY AT 75° F AS MANUFACTURED -5°–10° F 10°–30° F 30°–50° F 50°–70° F 70°–90° F -5° to 100° F 2 hrs. 350 psi 16 hrs. 800 psi 72 hrs.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories No waste • Sprays on in seconds • Fast setting Multi-Purpose Weather Gard Spray-On Rubber Film • Weatherproof Applications: • Forms a protective weatherproof seal on electrical connections • Electrical connections • Dries in minutes to crystal clear rubber film • Prevents corrosion on electrical connections • Recommended installation temperatures: 50° to 80° F • Outdoor lighting • Panel boxes • Pool mot
Cementing PVC Conduit: 1. Make square saw cut with fine-tooth saw. Carlon ® non-metallic products are joined by means of solvent cement joints. Sizes 1⁄2" through 11⁄2" should be cut square (using a fine-tooth handsaw) and deburred. For sizes 2" through 6", a miter box or similar saw guide should be utilized to keep the material steady. After cutting and deburring, wipe ends clean of dust, dirt and shavings.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Elbows, Sweeps and Accessories Installation Instructions — Fittings and Adapters for Terminating Non-Metallic Rigid Conduit Terminating Non-Metallic Rigid Conduit is quick and easy utilizing either of the methods indicated below. Terminations may be made in any electrical box or enclosure using standard size knockouts or drilled holes. Method 1.
White Diamond Braid Rope This rope is constructed of polyethylene over polyester, designed specifically for fiber optic pulling. The p olyethylene jacket has a “slippery” feel that gives less drag in pulling through conduit. CAT. NO. REEL LENGTHS (FT.) SB14105 5,000 DIAMETER (IN.) ⁄4 1 RECOMMENDED APPROXIMATE APPROXIMATE WORKING LOAD AVG. TENSILE STD. WT. (LBS.) (LBS.) (LBS.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Conduit Bodies and Fittings (for use with Schedule 40 and 80 Conduit) Standard Couplings Expansion Fittings E945 series expansion fittings are designed to compensate for length changes due to temperature variations in exposed conduit runs. LR33856 O.D.
Conduit Bodies and Fittings (for use with Schedule 40 and 80 Conduit) Female Adapters Sleeve Coupling (For Repair Work) No Internal Stop SIZE (IN.) STD. CTN. STD. WT. (LBS.) LENGTH (IN.) E948H E948J E948K E948L E948N E948P E948R E948JR E948JS E948KS7 E948L12 E948L6 E948LS E948N12 E948N7 E948NS E948PS E948R10 E948R12 E948RS 11⁄2 2 21⁄2 3 4 5 6 2 2 (Sch. 40 Split Duct) 21⁄2 (Sch. 40 Split Duct) 3 3 3 (Sch. 40 Split Duct) 4 4 4 (Sch. 40 Split Duct) 5 (Sch. 40 Split Duct) 6 6 6 (Sch.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Conduit Bodies and Fittings (for use with Schedule 40 and 80 Conduit) Plugs Adapters Adapts non-metallic conduit to all electrical enclosures by inserting adapter through knockout and cementing into Carlon couplings. Reducer Plugs L CM SIZE (IN.) STD. CTN. MIN D (IN.) OD (IN.) TYPICAL MAX X (IN.) E996D E996E E996F E996G E996H E996J E996K E996L E996N ⁄2 ⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4 100 100 100 50 50 25 15 20 10 .662 .824 1.049 1.380 1.
Conduit Bodies and Fittings (for use with Schedule 40 and 80 Conduit) Offsets E13938 Note: For vertical applications only. ØG Meter Offset ØH E CAT. NO. STD. CTN. E F G H E998D E998E E998E-CAR E998F E998F-CAR E998G-CAR E998H-CAR E998J-CAR E998K-UPC E998L E998N ⁄2 ⁄4 3 ⁄4 1 1 11⁄4 11⁄2 2 21⁄2 3 4 5 20 5 15 5 5 5 5 2 2 2 1.76 1.76 1.76 2.26 2.26 3.52 3.52 4.26 7.47 7.47 10.45 .45 .45 .45 .59 .59 .74 .74 .83 1.70 1.70 2.25 .45 .45 .45 .58 .58 .71 .71 .78 1.31 1.31 1.88 — — — — — .50 .50 .56 1.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Conduit Bodies and Fittings (for use with Schedule 40 and 80 Conduit) Flat Sealing Washers Where a waterproof termination is required into any enclosure (metallic or non-metallic), install the neoprene washer over the threads of a terminal adapter before inserting into the enclosure. Use a standard locknut or threaded bushing to secure the assembly. CAT. NO. SIZE (IN.) STD. CTN.
Conduit Bodies and Fittings (for use with Schedule 40 and 80 Conduit) Conduit Bodies Type LB Type LR Q LR31146 L1 L2 Note: Covers are not sold as separate item. W H L1 L2 L3 W DIMENSIONS (IN.) CAT. NO. SIZE STD. TYPICAL MAX. (IN.) CTN.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Switch and Junction Boxes Molded Non-Metallic Junction Boxes — 6P Rated Non-metallic junction boxes are UL Listed with a NEMA 6P rating per Section 314.29, Exception of the National Electrical Code® and CSA Certified per Section 12 of the Canadian Electrical Code.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Switch and Junction Boxes Large PVC Junction Boxes — NEMA 4X Large PVC Junction Boxes are fabricated from Type II PVC sheet using a unique technology. Reduce the use of steel boxes and keep your wiring connections clean, safe and dry using these high-quality, fully gasketed junction boxes.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Switch and Junction Boxes Single-Gang FS Boxes 5.70 (144.78) Type FSE 3.281 83.3 Type FSS 3.281 (83.34) .938 (23.83) 2.27 (57.5) 2.80 (71.1) Ø 0.2 5.1 2.87 73 DIA. TO FIT DESIGNATED CONDUIT SIZE 4.54 (115.3) 4.54 115.3 3.87 98.4 DIA. TO FIT DESIGNATED CONDUIT SIZE 0.43 10.9 .43 (11) 2.42 61.5 2.30 61.
Type FD LR31146 Where noted by Type FDC 2 7⁄8" 3.281 83.3 2 7⁄8" 2 17⁄32" 3 7⁄8" E11461 2 7⁄8" 3 3⁄8" CL 0.938 TYP 23.8 2.8 71.1 4 5⁄8" 0.43 11 DIA. TO FIT DESIGNATED CONDUIT SIZE Ø 0.2 5.1 2.87 73 4.54 115.3 3.87 98.4 3.37 85.7 0.43 11 2 3⁄4" 2.99 75.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Switch and Junction Boxes LR31146 Where noted by Two-Gang FS Boxes E11461 • For dead-end terminations where two devices or additional wiring capacity is required • For through terminations where two devices or additional wiring capacity is required • All sizes take standard covers and accessories or devices • All sizes take standard covers and accessories or devices • Integral mounting feet provide easy mounting • Integral mounting feet p
Straps, Clamps and Accessories Snap Strap Conduit Support Straps Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ™ Carlon’s Snap Strap™ offers a unique support strap designed especially for the installation of PVC conduit. Also usable for installations of rigid steel. This highstrength, non-metallic clamp enables conduit to expand and contract freely, eliminating the bowing commonly seen from the expansion and contraction of conduit caused by varying temperature changes.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Straps, Clamps and Accessories Non-Metallic Clamps Non-metallic clamps offer the same chemical resistance as Carlon ® non-metallic conduits for a complete, corrosion-resistant system. To be used in accordance with conduit spacing requirements per NEC® Section 352.30 and 12-1114 of the CEC. • UV inhibited for use in direct sunlight NEC and National Electrical Code are registered trademarks of the National Fire Protection Association, Inc.
Straps, Clamps and Accessories Carlon Masonry Pipe Clamps Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® Carlon ® Masonry Pipe Clamps make installations faster and easier by eliminating the use of bolts and anchors. The one-piece design features an anchoring projection designed to push into a 5⁄16" drill hole. The clamps are used to securely support pipe/conduit and electrical cables on concrete and masonry block, and unlike metallic clamps Carlon ® Masonry Clamps won’t rust or corrode.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Straps, Clamps and Accessories Slip Meter Risers Carlon® Slip Meter Risers are designed for use in electrical service entrance applications. They provide solutions for applications requiring a non-rigid connection, with incoming service conduit diameters ranging from 2" to 4". The Slip Meter Risers are fitted with a terminal adapter for easy installation at the service entrance location and provide a low-cost method to comply with NEC® 300.
® ® Carlon® Snap-Loc® Duct Spacers provide stability, consistent separation and relieve direct stress for duct materials encased in concrete and direct-burial applications. Carlon® Snap-Loc® Spacers provide: • A side dovetail rail-and-groove design enabling side-by-side interchangeability of conduit spacer sizes while maintaining horizontal stability • Locking keyways incorporated into intermediate spacers eliminate the need for costly top spacers in each size.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Spacers Carlon Snap-Loc Spacers (continued) ® ® Dimensions — Base Spacers Dimensions — Intermediate Spacers CAT. NO. SIZE (IN.) A (IN.) C (IN.) S288JHN S288JJN S288JLN S288LHN S288LJN S288LLN S288NFN S288NHN S288NJN S288NLN S288PHN S288PJN S288PLN S288RHN S288RJN S288RLN S288SHN S288SJN 2 x 11⁄2 2x2 2x3 3 x 11⁄2 3x2 3x3 4x1 4 x 11⁄2 4x2 4x3 5 x 11⁄2 5x2 5x3 6 x 11⁄2 6x2 6x3 8 x 11⁄2 8x2 4.25 4.25 4.25 4.81 4.81 4.81 4.50 5.31 5.31 5.
® ™ Carlon® Snap-N-Stac™ Combo Duct Spacers are specifically designed to replace the two-piece base and intermediate spacer system, by combining the conventional base and intermediate spacer into a single unit. Manufactured out of highly engineered thermoplastic material, Snap-N-Stac™ Spacers are strong, durable and able to withstand the rigors of concrete construction. They feature an innovative horizontal and EXCLUSIVE vertical locking system, and can be used as either a base or intermediate spacer.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Spacers Carlon Snap-N-Stac Combo Spacers (continued) ® ™ Installation Instructions IMPORTANT: 1. Snap-N-Stac™ Spacers are recommended for concrete-encased applications only. 2. T he use of duct spacers for direct burial may result in excessive point deflections unless proper design engineering is applied, such as the proper compaction of the appropriate backfill material.
Spacers Vertical Free Standing Reducer If spacers are installed using free-standing method, it is recommended to install the spacer on the upper row mid-way between the two spacers on the bottom row. 1" and 2" Snap-Loc® Reducers enable fixturing of 1" and 2" conduit inside of larger spacers. Transition to Various Duct Sizes Install spacers side-by-side by inserting the male adapter into the female adapter. Note: All Snap-N-Stac™ spacers are designed to interlock horizontally, regardless of size.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Spacers Carlon Snap-N-Stac Combo Spacers ® ™ CAT. NO. DESCRIPTION SP2W20-1 SP2W30-1 SP4W15-1 SP4W20-1 SP4W30-1 SP2W20-2* SP2W30-2* SP3W20-2 SP3W30-2 SP4W15-2* SP4W20-2* SP4W30-2* SP5W20-2 SP5W30-2 SP6W20-2 SP6W30-2 SP2W20-3 SP2W30-3 SP4W15-3 SP4W20-3 SP4W30-3 SIZE (IN.) SEPARATION (IN.) STD. CTN. STD. WT. (LBS.
P&C Flex Conduit and Fittings Carlon P&C Flex Corrugated Flexible Conduit ® ® Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® Carlon® P&C Flex® Non-Metallic Corrugated Conduit makes power and communication installations faster and easier by providing maximum installation flexibility. The corrugated design is flexible enough to accommodate any degree of bend requirement. Unlike rigid conduit, it has a tight bend radius, making this product ideal for shallow trenches.
P&C Flex Conduit and Fittings Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® P&C Flex® Conduit Terminal Adapters CAT. NO. SIZE (IN.) I.D. (IN.) O.D. (IN.) PULL TAPE REEL/ COIL STD. CTN. (FT.
P&C Flex Conduit and Fittings ® PERFORMANCE PROPERTIES ⁄4" 1" 11⁄4" 11⁄2" 2" 21⁄2" 3" 4" 200 35 5 6 200 200 40 8 6 300 200 40 8 6 400 200 50 15 7 500 200 50 25 8 700 130 70 35 12 1000 130 120 60 15 1500 90 140 60 18 2000 3 Stiffness F/ y at 5% deflection Impact Strength (ft./lbs.) 72° F Impact Strength (ft./lbs.) 32° F Minimum Bending Radius (inches) Conduit Tensile Strength Storage: -4° to 158° F Handling: -4° to 104° F Sweep and Elbow Conversion Chart RADIUS (IN.) NOM. DIA.
P&C Flex Conduit and Fittings Suggested Applications Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® • Carlon ® P&C Flex ® Non-Metallic Corrugated Conduit is the most versatile system available for power and communications applications • P&C Flex ® combines high crush strength with flexibility.
P&C Flex Conduit and Fittings ® Correct Method Incorrect Method Lay conduit in the trench as straight as possible. Avoid undulations up and down and side to side. Trenching Secure end Spot backfill Keep bends as gradual as possible 1 Stretch duct in one direction away from secured end 4 Trenching Trench should be graded true and free from stones or soft spots. Backfill should also be free of stones and be firmly tamped around the sides of the conduit to develop maximum supporting strength.
Carflex Liquidtight Flexible Conduit and Fittings Carflex Liquidtight Flexible Non-Metallic Conduit Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® ® Liquidtight Flexible Non-Metallic Conduit provides superior wire protection in harsh, damp environments. Carflex® Conduit is non-conductive, noncorrosive and resistant to oil, acid, ozone and alkaline. Carflex® Conduit is strong and lightweight and, because it weighs 50% less than metallic systems, it’s easy to handle, transport and install.
Carflex Liquidtight Flexible Conduit and Fittings Carflex X-Flex Non-Metallic Mechanical Protection Tubing ® ™ Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® Extra-Flexible Non-Metallic Mechanical Protection Tubing is ideal for applications requiring extra strength and flexibility, such as robotics and repetitive-flexing arms. Carflex® X-Flex™ is non-conductive, non-corrosive and resistant to oil, acid, ozone and alkaline.
Carflex Liquidtight Flexible Conduit and Fittings For use with Carflex conduit and Carflex X-Flex tubing. Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® ® ® Typ.
Carflex Liquidtight Flexible Conduit and Fittings For use with Carflex conduit and Carflex X-Flex tubing. ® ® Typ. Dimension with Carflex Installed ™ Body Carflex Liquidtight 90° Fittings D C ® B Nitrile Rubber O-Ring Fitting Body Assembly Compression Nut O-Ring Locknut A Extended Threads Compression Nut E F Metal Locknut LT20C-CAR, LT20F Typ.
Carflex Liquidtight Flexible Conduit and Fittings Carflex One-Piece Liquidtight Fittings Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® ® Unique Design The simple, one-piece body design of the Carflex® One-Piece Liquidtight Non-Metallic Fitting requires no disassembly of components for installation. The system is so strong that there is no need for a compression nut. PVC Construction PVC construction of the fitting and locknut provides unparalleled protection from water, oil and dust.
Carflex Liquidtight Flexible Conduit and Fittings ® ® • No threading of the conduit or tubing required to install A • Complete conduit/connector system is reusable • Lower installed cost Features: C Suggested Clearance Hole for Non-Threaded Mounting • Suitable for indoor/outdoor use • Gray connectors provided with assembled O-ring and metal locknuts • All-nylon construction resists saltwater, weak acids, gasoline, alcohol, oil, grease and common solvents • Molded of type 6/6 nylon.
Carflex Liquidtight Flexible Conduit and Fittings Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® Carflex Fittings Installation Instructions ® LT43C-CAR, LT43F thru J, LT20C-CAR, LT20F thru J. LT43D-NEW, LT43E-NEW, LT20D-NEW, LT20E-NEW. 1. Cut the end of the Carflex® conduit or Carflex® X-Flex™ tubing square. 1. Cut the end of the Carflex® conduit or Carflex® X-Flex™ tubing square. 2. Install compression nut and sealing gland ring over the end of the conduit or tubing. 2.
Carflex Liquidtight Flexible Conduit and Fittings ® Carflex Liquidtight Whips Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings ® Carflex® Liquidtight Whip assemblies save the customer time and hassle of having to hunt for the needed components. Our moisture-tight non-metallic flexible conduit system is ideal for installing swimming pool motors, hot tubs, spas, air conditioners, pumps, outdoor lighting and more.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings Technical Information Typical Properties of Conduit Raw Material Compound THERMAL ASTM TEST TYPICAL VALUES MECHANICAL ASTM TEST TYPICAL VALUES Co-effecient of Thermal Expansion-inch/ inch/° F (properties @ 73.4° F) Heat Distortion ° F at 264 psi Thermal Conductivity BTU (hr.) (ft.) (° F/in.) D696 3.38 x 10-5 D648 N/A 160° F 1.3 Specific Gravity Tensile Strength (psi) @ 73.4° F Izod Impact ft lbs./in.
Determine the Piston Opening Temperature Considerations for Rigid Non-Metallic Conduit Compensation for Linear Expansion Like all construction materials, PVC will expand or contract with variations in temperatures. The coefficient of linear expansion in PVC conduit is 3.38 x 10-5 in./in./°F as compared to 1.2 x 10-5 for aluminum and .6 x 10-5 for steel An expansion fitting is needed whenever the change in length due to temperature variation will be 1⁄4 in. or greater per 352.44 of the NEC.
Conduit & Fittings — Carlon® PVC Elbows, Conduit & Fittings E-518 Technical Information Corrosion Resistance of Carlon Schedule 40 and Schedule 80 Fittings ® Carlon Schedule 40 and Schedule 80 Fittings are generally acceptable for use in environments containing the chemicals below. These environmentalresistance ratings are based upon tests where the specimens were placed in complete submergence in the reagent listed.