Conduit & Fittings — Carlon
®
PVC Elbows, Conduit & Fittings
Sweep and Elbow Conversion Chart
RADIUS
(IN.)
NOM. DIA. SEGMENT
18" REQUIRED
LENGTH OF P&C FLEX (IN.)
24"
REQUIRED
LENGTH OF P&C FLEX (IN.)
36" REQUIRED
LENGTH OF P&C FLEX (IN.)
48" REQUIRED
LENGTH OF P&C FLEX (IN.)
60" REQUIRED
LENGTH OF P&C FLEX (IN.)
1
1
2
90° 33 42 61 80 99
45° 19 23 33 42 52
30° 14 17 23 30 36
22
1
2° 12 14 19 23 28
2
90° 32 42 61 79 98
45° 18 23 32 42 51
30° 14 17 23 29 35
22
1
2° 11 12 18 23 28
2
1
2
90° 34 44 63 81 100
45° 20 25 33 44 53
30° 16 19 24 31 37
22
1
2° 13 15 20 25 30
3
90° 35 44 63 82 101
45° 20 25 34 44 53
30° 16 19 24 32 38
22
1
2° 13 16 20 25 30
4
90° 37 46 65 84 103
45° 22 27 37 46 55
30° 18 21 27 34 40
22
1
2° 15 18 22 27 32
For other radius sweeps, use this formula: .0175 x Radius (inches) x Angle° = Required length of P&C Flex in inches.
Technical Information
P&C Flex
®
conduit is flexible. Carlon
®
P&C
Flex
®
Non-Metallic Corrugated Conduit is used
to transition from Carlon
®
P&C Duct Type DB.
Despite equipment being mounted away from
the pole, P&C Flex
®
conduit remains flush to
the pole.
Flex Conduit
Flex Conduit
Coupling
Coupling
Coupling
Rigid Non-
Metallic Conduit
Customer Conduit
Guard
When soil conditions do not permit
direct burial of cable, use Carlon
®
P&C
Flex
®
Non-Metallic Corrugated Conduit
to protect the cable. A lower coefficient
of friction provides easy wire pulls on
location. Flexibility eliminates the need
for elbows.
Specifications
PERFORMANCE PROPERTIES
3
4" 1" 1
1
4" 1
1
2" 2" 2
1
2" 3" 4"
Stiffness F/ y at 5% deflection 200 200 200 200 200 130 130 90
Impact Strength (ft./lbs.) 72° F 35 40 40 50 50 70 120 140
Impact Strength (ft./lbs.) 32° F 5 8 8 15 25 35 60 60
Minimum Bending Radius (inches) 6 6 6 7 8 12 15 18
Conduit Tensile Strength 200 300 400 500 700 1000 1500 2000
Storage: -4° to 158° F
Handling: -4° to 104° F
Carlon
®
P&C Flex
®
Non-Metallic Corrugated Conduit protects control cables
in supervisory control and data acquisition equipment (SCADA) in distribution
substations. Flexibility provides maximum utilization of equipment.
Substation SCADA
RTU cabinet
Steel channels to support
RTU and provide space
under cabinet for conduit
Carlon
®
Terminal Adapters
cemented to ends of P&C Flex
®
Circuit Safe
®
JIC Enclosure
with transducers and interposing
relays mounted to steel structure
or equipment
Conduit clamps
Control Cables run in 1" or 1
1
2"
P&C Flex
®
conduit
P&C Flex
®
Conduit and Fittings