2.0 Warnings 
Disconnect all power 
sources 
Electricity can be very dangerous. 
Installation should be performed 
only by a licensed electrician or 
qualified personnel. 
Battery and wiring 
safety 
Observe all safety precautions of 
the battery manufacturer when 
handling or working around 
batteries. When charging, batteries 
produce hydrogen gas, which is 
highly explosive.  
Wiring connections 
Ensure all connections are tight 
and secure. Loose connections 
may generate sparks and heat. Be 
sure to check connections one 
week after installation to ensure 
they are still tight. 
Work safely 
Wear protective eyewear and 
appropriate clothing during 
installation. Use extreme caution 
when working with electricity and 
when handling and working around 
batteries. 
Observe correct 
polarity 
Reverse polarity of the battery 
terminals will cause the controller 
to give a warning tone. Reverse 
connection of the array will not 
cause an alarm but the controller 
will not function. Failure to correct 
this fault could damage the 
controller. 
Do not exceed the 
GP-PWM-30 Amp 
current and max 
voltage ratings 
The current rating of the solar 
system is the sum of the Maximum 
Power Current (Imp) of the solar 
PV strings in parallel. The resulting 
system Imp current is not to 
exceed 30A. The voltage of the 
array is the rated open circuit 
voltage (Voc) of the PV array and 
is not to exceed 28V. If your solar 
system exceeds these ratings, 
contact your dealer for a suitable 
controller alternative. 