In this parameter the IDN of that parameter is entered to which a value
corresponding to the voltage at the respective analog input is to be
written. The scaling is made via P-0-0214, Analog input, assignment A,
scaling per 10V full scale!
Note: Only such IDNs can be entered in P-0-0213 that are contained
in P-0-0212, Analog input, list of assignable parameters.
See also Functional Description "Analog Interface"
See also Functional Description "Analog Inputs"
P-0-0214, Analog input, assignment A, scaling per 10V
full scale
Input min/max: Default value: Unit:
MPB: --- / --- 0 --
By means of this parameter the analog input for assignment A (range of
values per 10 V) is scaled.
Unit, decimal places and data type are determined by the parameter
assigned in P-0-0213, Analog input, assignment A, target parameter.
See also Functional Description "Analog Interface"
See also Functional Description "Analog Inputs"
P-0-0215, Analog input, assignment A, signal value at 0V
Input min/max: Default value: Unit:
MPB: --- / --- 0 --
In this parameter the reference of the analog input for assignment A
(value with a voltage of 0 V at the analog input) is defined. This allows
compensating a possible offset of the voltage at the analog input for
assignment A.
Unit, decimal places and data type are determined by the parameter
assigned in P-0-0213, Analog input, assignment A, target parameter.
See also Functional Description "Analog Interface"
See also Functional Description "Analog Inputs"
P-0-0216, Analog input, assignment A, dead zone
Input min/max: Default value: Unit:
MPB: 0,000 / 10,000 0,000 V
By means of this parameter it is possible to define, for the analog input
voltage (assignment A), a range of values that is interpreted as voltage
value 0 V ("dead zone") by the drive controller.
See also Functional Description "Analog Interface"