User Manual

Carrier
Application Data
Application Detail
16JB
5qP£È.S<£ù£5 ¡sy
Hermetic Absorption Liquid Chillers
GENERAL
Application details in this publication cover
various methods of applying the 16JB absorption
machine to meet liquid chilling needs. Throughout
this publication, the chilled liquid will be water.
Subjects covered are chilled water temperature
control, condenser water temperature control,
system design for steam and hot water machines,
and general information.
CHILLED WATER TEMPERATURE CONTROL
The absorption machine is basically a water
chiller that can be connected to any conventional
open or closed system. However, circulation of
chilled water must be continuous during operation
of the machine and during the shutdown dilution
cycle. Chilled water flow may be restricted at
partial load.
For fine chilled water temperature control
within narrow limits, such as required in precision
control of industrial processes or maintenance of
laboratory conditions, the chilled water system
may require additional storage volume to allow the
machine to adjust slowly to changes in load.
Normal air-conditioning applications are not
subject to such requirements.
Systems having large storage volumes of chilled
water transmit load changes to the machine slowly,
allowing accurate chilled water temperature con
trol. Small storage systems transmit load changes
rapidly, making temperature control more diffi
cult. For fine temperature control, the chilled
water system volume should be at least ten times
the gpm flow through the cooler. If a tank is added
to the system for extra storage volume, it should
be located in the line from the load to the cooler.»
Two-Pipe Cooling-Heating Systems When
machines are used in conjunction with a two-pipe
cooling-heating system, certain precautionary steps
should be taken during changeover from heating to
cooling.
Maximum water temperature permitted thru
the evaporator is 130 F because of the possibility
of tube stress. If system water temperature is above
80 F but less than 130F at changeover time,
evaporator flow should be throttled to prevent
machine overload.
It is recommended that hot water temperatures
be reset, based on outside air temperature. If a
reset-type control is used, the entering hot water
temperature at changeover will normally be lower
than 130 F.
STEAM MACHINES
Boilers Generally, any boiler capable of modu
lating its input to maintain design operating steam
pressure within 1 psi under varying loads, is suit
able for application with the absorption machine.
This generally includes all gas- and oil-fired boilers.
Some oil-fired boilers are conversions from
coal-fired to oil-fired and may have control systems
which are too sluggish to give proper response to
machine load changes. Direct control of oil feed
rate normally ensures proper response.
Coal-fired boilers, due to slow buildup and
shutdown characteristics, should be used only
when the absorption machine represents less than
15% of boiler operating load. This generally limits
coal-fired boiler applications to large industrial jobs
where process steam is generated in large quantities
year-round.
BOILER CAPACITY — Minimum boiler capacity
for use with the absorption machine is equal to full
load steam consumption, plus sufficient capacity
to offset piping radiation losses. In the absence of a
detailed study of radiation and vent losses, a
minimum 10% safety factor should be used.
Pressure Reducing Valves Maximum unit ratings
are based on 14 psig steam pressure at the
generator inlet. Operation at higher inlet pressures
or with more than 100 F superheat is not per
missible. Higher inlet pressures may lead to over
concentration.
Where steam supply pressures are above 15 psig
(14 psig + 1 psig for control) and below 20 psig,
the steam control valve can be used to reduce the
pressure. If steam supply is above 20 psig, a
pressure reducing valve must be provided between
the steam supply and the control valve inlet. A
safety relief valve should be provided between the
steam control valve and the generator inlet. This
valve must be set in accordance with paragraph
UG-133 (f) of the ASME code to relieve at a
pressure not exceeding 17 to 18 psig or the setting
determined by apphcable local codes.
Further specific details relative to pressure
reducing stations should follow accepted standards,
such as the ASHRAE Guide and manufacturer’s
recommendation. For applications on high-pressure
district heating, the steam utility should be con
sulted for local codes or standards.
Steam Piping should be sized to avoid excessive
pressure drop or excessive velocities. Recommenda
tions and pipe sizing tables are given in the Carrier
System Design Manual. It is recommended that
lines be sized on the basis of design system flow for
the machine plus a 10 to 20% safety factor to
allow for normal radiation losses.
© Carrier Corporation 1971
Form 16JB-2XA

Summary of content (11 pages)