Service manual

96
30AW
Carrier interfaces
7
11 ( )
OUTDOOR
TEMPERATURE
This code displays the Outdoor Air Temperature. The valid OAT
value is used with this priority:
1. OAT from GMC thermistor (if it is installed)
2. OAT from inverter, read by TO sensor.
-30°C 90°C -
12
( )
GMC OUTDOOR AIR
TEMPERATURE
This code displays the Outdoor Air Temperature read by GMC
thermistor.
-- -
13
TEMPERATURE ROOM
SENSOR ADJUSTMENT
This code is use to adjust the temperature read by the sensor in
order to recover bad positioning of the user interface.
-5°C +5°C 0°C
14 DAY PERIOD
This code is use to select how many period per day will be availa-
ble for the scheduling:
2
4
6
26 4
15
HOME HEAT TEMPE-
RATURE
With this code the User can select the HOME Temperature set-
point in Heating Mode
12°C 38°C 20°C
16
HOME COOL TEMPE-
RATURE
With this code the User can select the HOME Temperature set-
point in Cooling Mode
12°C 38°C 24°C
17
SLEEP HEAT
TEMPERATURE
With this code the User can select the SLEEP Temperature set-
point in Heating mode
12°C 38°C 18°C
18
SLEEP COOL
TEMPERATURE
With this code the User can select the SLEEP Temperature set-
point in Cooling Mode
12°C 38°C 26°C
19
AWAY HEAT
TEMPERATURE
With this code the User can select the AWAY Temperature set-
point in Heating mode
12°C 38°C 15°C
20
AWAY COOL
TEMPERATURE
With this code the User can select the AWAY Temperature set-
point in Cooling Mode
12°C 38°C 28°C
21
( )
USER ROOM
SET-POINT
This code displays the room set-point that the user, pressing the
temporary/hold button, is selecting as temporary or hold.
12°C 38°C 20°C
22
( )
FAULT CODE
This code displays the last fault code occurred.
-- -
23
( )
FAULT HISTORY
This code displays the recent 4 fault codes stored.
-- -
100 SYSTEM TYPE
This code is use to set the System type:
1. A2W Monobloc xed Water Temperature Value (dry contacts)
2. A2W Monobloc Climatic Curve setup (dry contacts)
3. A2W Monobloc Comfort with NUI
4. A2W Monobloc Comfort with NUI as Thermostat
5. N.A.
6. A2W Monobloc RS485
7. N.A.
1 7 1. A2W
101 USER INTERFACE TYPE
This code is use to dene if NUI User Interface is used and how it
is used:
0. Not Used (Input Relay active/SUI)
1. NUI Installed
2. NUI used as programmer
0 2 0. Not used
102
( )
NUI SOFTWARE
RELEASE
This code displays the NUI Software Release
-- -
103
( )
NUI SOFTWARE
VERSION
This code displays the NUI Software Version
-- -
104 OUTPUT TEST
This code is use to force Output ON to test (max 10 minutes):
0 9 0. No test
0. No test
1. Water pump
2. Alarm / Ambient temperature reached
3. External Heat Source / Defrost
4. Alarm + Defrost / Humidity
5. Trace Heater / Additional Water Pump
6. 3 Way valve
7. SUI Alarm
8. Blank
105
RESET PUMP
RUN-TIME
This code is use to reset the water pump timer to zero.
no yes no
106
EXTERNAL HEAT
SOURCE / DEFROST
This code is use to select the output connected at PIN 4 on
terminal strip:
1. External Heat Source
2. Defrost Output
12 1
107 HUMIDITY LIMIT
This code is use to dene the humidity threshold limit to enable
the output for the external de-humidier system.
20 100 
Code Nr. Name DESCRIPTION
VALUE RANGE
STANDARD
Min Max