Specifications

10
DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)
30GX 205-265
NOTE : Refer to certified dimensional drawings 99DI 205GX when designing an installation.
Weight distribution Total
at the twelve operating
mounting holes (kg) weight (kg)
30GX P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 PT
205 573 321 453 857 575 902 655 923 367 184 - - 5810
225 573 370 453 904 575 950 655 970 367 231 - - 6048
250 593 330 453 860 575 912 655 920 367 195 250 200 6310
265 593 382 453 906 575 962 655 970 367 243 250 200 6556
Notes :
1. Unit must have clearances for air flow as follows :
Top : do not restrict in any way
End and Side space required (from solid surface)
2. In case of multiple chillers (up to four units), the respective
clearance between them should be increased from 1830 to
2000 mm for the side space requirement.
3. Unit must have clearances for cooler tube removal as
follows :
Additional space required to remove cooler tubes
Electrical box
2000
1830
2000
1830
20002000
1525
1525
Multiple chiller installation (see note 2)
SOLID SURFACE AREASOLID SURFACE AREA