Specifications

11
DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)
30GX 280-350
NOTE : Refer to certified dimensional drawings 99DI 280GX when designing an installation.
Notes :
1. Unit must have clearances for air flow as follows :
Top : do not restrict in any way
End and Side space required (from solid surface)
2. In case of multiple chillers (up to four units), the respective
clearance between them should be increased from 1830 to
2000 mm for the side space requirement.
3. Unit must have clearances for cooler tube removal as
follows :
Additional space required to remove cooler tubes
Electrical box
2000
1830
2000
1830
20002000
1525
1525
Multiple chiller installation (see note 2)
SOLID SURFACE AREASOLID SURFACE AREA
Weight distribution Total
at the sixteen operating
mounting holes (kg) weight (kg)
30GX P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 PT
280 - - 400 300 650 900 650 900 550 900 650 900 300 203 - - 7303
295 - - 400 300 650 936 650 930 550 900 650 900 200 150 150 130 7496
325 300 200 300 200 640 920 630 920 533 920 640 920 200 150 150 130 7753
350 300 200 300 200 650 930 650 930 550 930 650 930 250 150 150 132 7852