Specifications

15
ELECTRICAL DATA
30HXC
30HXC 075 085 095 105 115 125 135 145 160 170 185
Mains power supply
Nominal voltage V-ph-Hz 400-3-50
Voltage range % ± 10
Control circuit voltage* V-ph-Hz 230-1-50
Nominal unit power input** kW 62.1 68 80.5 86.4 90.6 98.4 108.7 117.9 124 133 144.3
Nominal operating current** A 87 96 122 133 139 165 178 189 203 206 239
Maximum operating current*** A 142 157 175 195 210 228 255 275 302 300 330
Maximum starting current
Across the line start**** A 415 494 577 676 691 709 819 839 866 992 1021
Optional star delta start**** A 180 205 231 262 277 295 330 350 377 406 435
30HXC 215 250 265 280 300 315 340 370
Mains power supply
Nominal voltage V-ph-Hz 400-3-50
Voltage range % ± 10
Control circuit voltage* V-ph-Hz 230-1-50
Nominal unit power input** kW 171.8 192.3 204 216.3 229.2 246.5 263.1 289.2
Nominal operating current** A 308.0 327.9 342.5 360.3 398.5 416.2 443.3 480.9
Maximum operating current*** A
Circuit A 255 278 300 330 248 278 300 330
Circuit B 151 165 165 165 271 278 300 330
Maximum starting current
Across the line start**** A 970 1134 1156 1186 1099 1247 1292 1350
Optional star delta start**** A 481 548 570 600 610 661 706 764
Legend :
* Control power circuit is supplied through factory installed transformer
** Unit power input kW and current drawn at cooler entering/leaving temperature 12°C/7°C, condenser entering/leaving temperature 30°C/35°C and at 400 Volts nominal voltage
*** Maximum current drawn by compressors at full load and at minimum voltage 360 Volts
**** Maximum instantaneous starting current (maximum operating current of the smallest compressor + locked rotor amps of the largest compressor)
Compressor
PART NUMBER Tons LRA (Y) LRA (Delta) MHA
06NW 1146 S7 N 39 109 344 71
06NW 1174 S7 N 46 134 423 86
06NW 1209 S7 N 56 160 506 104
06NW 1250 S7 N 66 191 605 124
06NW 1300 S5 N 80 226 715 151
06NW 1209 S7 E 56 191 605 113
06NW 1250 S7 E 66 226 715 136
06NW 1300 S5 E 80 270 856 165
Legend :
LRA (Y) Locked Rotor Amps with optional star delta start
LRA (Delta) Locked Rotor Amps with standard across the line start
MHA Compressor Must Hold Amps (Maximum Operating Current at 360 V)
06NW Water-cooled condensing compressor
N Non Economized compressor
E Economized compressor