Specifications

28
FIELD POWER SUPPLY
30HXC 075-185
Electrical box
S mm
2
S mm
2
30HXC A (mm) B (mm) Min. Max.
075-115 125 236 70 120
125 125 236 95 120
135-185 136 200 120 185
S mm
2
S mm
2
30HXC A (mm) B (mm) B1 (mm) Min. Max.
075-115 70 40 25 70 120
125 70 40 25 95 120
135-185 70 62.5 40 120 300
15
Power terminal block Main disconnect switch
16
17
IMPORTANT
Before the connection of the main power cables (L1 - L2 - L3) on the power terminal block, it is imperative to check the right order
of the 3 phases before proceeding to the connection on the terminal block or the main disconnect switch.
FIELD CONTROL WIRING
Refer to the Certified Electrical Wiring Diagram supplied with
the unit for the field control wiring of the following features :
- Cooler pump interlock (mandatory)
- Remote on/off switch
- Condenser Flow Switch (Field supplied)
- Remote Heat / Cool switch
- Demand limit external switch 1
- Demand limit external switch 2
- Remote dual set point
- General alarm contact
- Cooler pump control (Option)
- Condenser pump control (Option)
- Outdoor air temperature (Option)
- Remote Reset 4-20 mA (Option)
- Demand limit 4-20 mA (Option)
PE M10
GROUND FIELD
CONNECTION
PE M10
GROUND FIELD
CONNECTION
PE M10
GROUND FIELD
CONNECTION