Specifications

33
FIELD POWER SUPPLY (CONT.)
30GX 205-265
Electrical box
SA mm
2
SB mm
2
30GX Min. Max. Min. Max.
205 240 300 95 185
225 240 300 120 185
250 2x120 2x185 120 185
265 2x150 2x185 120 185
SA mm
2
SB mm
2
30GX Min. Max. Min. Max.
205 240 300 95 120
225 240 300 120 300
250 2x120 2x300 120 300
265 2x150 2x300 120 300
Power terminal block Main disconnect switch
IMPORTANT
Before the connection of the main power cables (L1 - L2 - L3) on the power terminal block, it is imperative to check the right order
of the 3 phases before proceeding to the connection on the terminal block or the main disconnect switch.
FIELD CONTROL WIRING
Refer to the Certified Electrical Wiring Diagram supplied with
the unit for the field control wiring of the following features:
- Cooler pump interlock (mandatory)
- Remote on/off switch
- Remote Heat / Cool switch
- Demand limit external switch 1
- Demand limit external switch 2
- Remote dual set point
- General alarm contact
- Cooler pump control (Option)
- Outdoor air temperature (Option)
- Remote Reset 4-20 mA (Option)
- Demand limit 4-20 mA (Option)
PE M12
GROUND FIELD
CONNECTION
PE M12
GROUND FIELD
CONNECTION