Specifications
43
STATUS (CONT.)
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
<↓> 2 CHLLR COMM FAILURE
<↓> CIR A LOW DISCHG SUPERHT
<↓> CIR B LOW DISCHG SUPERHT
<↓> CIR A HIGH SDT
<↓> CIR B HIGH SDT
10 Capacity Control <10><STAT> CAPACITY CONTROL
<↓> Load/Unload Factor Displays xxx.x %
<↓> Control Point Displays xx.x °C
<↓> Leaving Water Temp Displays xx.x °C
<↓> MISC. INDICATORS
<↓> Liquid Lvl Sensor Cir. A Displays xx.x °C
<↓> Liquid Lvl Sensor Cir. B Displays xx.x °C
TEST (CONT.)
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
3 Unit Discrete <3><TEST> UNIT DISCRETE OUTPUT.
Output <↓> Fan 1
<↓> Fan 2
<↓> Fan 3
<↓> Fan 4
<↓> Fan 5
<↓> Fan 6
<↓> Cooler Pump Similarly, use
<↓> Condenser Pump <1><ENTR> to test
<↓> Cooler Heater remaining outputs.
<↓> Alarm Press the down
<↓> Remote Alarm 1 arrow key or
<↓> Remote Alarm 2 <0><ENTR> to turn
<↓> Remote Alarm 3 an output off.
<↓> Remote Alarm 4
<↓> Remote Alarm 5
<↓> Remote Alarm 6
<↓> Remote Alarm 7
<↓> Remote Alarm 8
<↓> Remote Alarm 9
<↓> Remote Alarm 10
<↓> Remote Alarm 11
<↓> Remote Alarm 12
<↓> Remote Alarm 13
<↓> Remote Alarm 14 *Output will display
<↓> Remote Alarm 15 Relay is ABSENT
<↓> Remote Alarm 16 when not configured
Test function and subfunctions
The test function operates the diagnostic program. To initiate the
test function, the LOCAL/OFF/REMOTE switch must be in the
OFF position.
To reach a particular test, press its subfunction number followed
by the Enter key then scroll to the desired test by pressing the
down arrow key.
TEST
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
1 Circuit A Discrete <1><TEST> CIRCUIT A DISCRETE OUTPUT
Output <↓> Loader A1
relay is OFF
<1><ENTR> Loader A1
relay is ON
<↓> Loader A2 Similarly, use
<1><ENTR> to test
remaining outputs.
Press the down
arrow key or
<0><ENTR> to turn
an output off.
<↓> Minimum load Valve A
<↓> Circuit A Oil Heater
<↓> A1 Mtr. Cooling Solenoid
<↓> A2 Mtr. Cooling Solenoid
<↓> Circuit A Oil Pump
<↓> Oil Solenoid A1
<↓> Oil Solenoid A2
*Output will display
Relay is ABSENT
when not configured
2 Circuit B Discrete <2><TEST> CIRCUIT B DISCRETE OUTPUT
Output <↓> Loader B1
relay is OFF
<1><ENTR> Loader B1
relay is ON
<↓> Loader B2 Similarly, use
<1><ENTR> to test
remaining outputs.
Press the down
arrow key or
<0><ENTR> to turn
the output off.
<↓> Minimum load Valve B
<↓> Circuit B Oil Heater
<↓> B1 Mtr. Cooling Solenoid
<↓> B2 Mtr. Cooling Solenoid
<↓> Circuit B Oil Pump
<↓> Oil Solenoid B1
<↓> Oil Solenoid B2
*Output will display
Relay is ABSENT
when not configured