Specifications

43
STATUS (CONT.)
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
<> 2 CHLLR COMM FAILURE
<> CIR A LOW DISCHG SUPERHT
<> CIR B LOW DISCHG SUPERHT
<> CIR A HIGH SDT
<> CIR B HIGH SDT
10 Capacity Control <10><STAT> CAPACITY CONTROL
<> Load/Unload Factor Displays xxx.x %
<> Control Point Displays xx.x °C
<> Leaving Water Temp Displays xx.x °C
<> MISC. INDICATORS
<> Liquid Lvl Sensor Cir. A Displays xx.x °C
<> Liquid Lvl Sensor Cir. B Displays xx.x °C
TEST (CONT.)
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
3 Unit Discrete <3><TEST> UNIT DISCRETE OUTPUT.
Output <> Fan 1
<> Fan 2
<> Fan 3
<> Fan 4
<> Fan 5
<> Fan 6
<> Cooler Pump Similarly, use
<> Condenser Pump <1><ENTR> to test
<> Cooler Heater remaining outputs.
<> Alarm Press the down
<> Remote Alarm 1 arrow key or
<> Remote Alarm 2 <0><ENTR> to turn
<> Remote Alarm 3 an output off.
<> Remote Alarm 4
<> Remote Alarm 5
<> Remote Alarm 6
<> Remote Alarm 7
<> Remote Alarm 8
<> Remote Alarm 9
<> Remote Alarm 10
<> Remote Alarm 11
<> Remote Alarm 12
<> Remote Alarm 13
<> Remote Alarm 14 *Output will display
<> Remote Alarm 15 Relay is ABSENT
<> Remote Alarm 16 when not configured
Test function and subfunctions
The test function operates the diagnostic program. To initiate the
test function, the LOCAL/OFF/REMOTE switch must be in the
OFF position.
To reach a particular test, press its subfunction number followed
by the Enter key then scroll to the desired test by pressing the
down arrow key.
TEST
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
1 Circuit A Discrete <1><TEST> CIRCUIT A DISCRETE OUTPUT
Output <> Loader A1
relay is OFF
<1><ENTR> Loader A1
relay is ON
<> Loader A2 Similarly, use
<1><ENTR> to test
remaining outputs.
Press the down
arrow key or
<0><ENTR> to turn
an output off.
<> Minimum load Valve A
<> Circuit A Oil Heater
<> A1 Mtr. Cooling Solenoid
<> A2 Mtr. Cooling Solenoid
<> Circuit A Oil Pump
<> Oil Solenoid A1
<> Oil Solenoid A2
*Output will display
Relay is ABSENT
when not configured
2 Circuit B Discrete <2><TEST> CIRCUIT B DISCRETE OUTPUT
Output <> Loader B1
relay is OFF
<1><ENTR> Loader B1
relay is ON
<> Loader B2 Similarly, use
<1><ENTR> to test
remaining outputs.
Press the down
arrow key or
<0><ENTR> to turn
the output off.
<> Minimum load Valve B
<> Circuit B Oil Heater
<> B1 Mtr. Cooling Solenoid
<> B2 Mtr. Cooling Solenoid
<> Circuit B Oil Pump
<> Oil Solenoid B1
<> Oil Solenoid B2
*Output will display
Relay is ABSENT
when not configured