Specifications

44
TEST (CONT.)
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
4 Valves and <4><TEST> VALVES AND MOTOR MASTER
Motor Master <> Circuit A EXV Valve
Target Percent = 0 %
<1><ENTR> CIRCUIT A EXV VALVE
Target Percent = 25 % Step in 25%
increments. EXV
may be moved to a
specific percent by
entering the desired
value and pressing
<ENTR>. Wait 30
seconds between
each step for valve
to stop moving.
<1><ENTR> CIRCUIT A EXV VALVE
Target Percent = 50 % Valve may be closed
in 25% increments
by keying in
<0><ENTR>. Wait
30 seconds between
each step for valve
to stop moving.
<1><ENTR> CIRCUIT A EXV VALVE
Target Percent = 75 %
<1><ENTR> CIRCUIT A EXV VALVE
Target Percent = 100 %
Target Percent = 0 %
<> Circuit B Water Valve Test same method
as for Circuit A.
<5><0><ENTR> CIRCUIT A WATER VALVE Test same method
as for EXV valves.
Target Percent = 50 %
<> Circuit A% Fan Speed Test same method
as for EXV valves.
<> Circuit B% Fan Speed Test same method
as for EXV valves.
Schedule function
The schedule function key is used to configure the occupancy
schedule.
This function provides a means to automatically switch the chiller
from an occupied mode to an unoccupied mode.
The schedules consist of eight user-configurable occupied time
periods. The control supports time schedules for local control,
remote control and ice building. These time periods can be flagged
to be in effect or not in effect on each day of the week and for
holidays (30 days).
Ice build control automatically sets the chilled water/brine control
point of the machine to a temperature where an ice building
operation for thermal storage can be accomplished.
Service function
This function allows the technician to view and input configuration
data. Factory configuration data (subfunction 1) cannot be
modified.
Options configuration 1 and 2 (subfunctions 2 & 3) as well as all
the other subfunctions, reset/demand limit (subfunction 4), factory
configuration codes (subfunction 5), transducer calibration
(subfunction 7), manual control (subfunction 8) will need a
password to be entered.
SERVICE
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
1 Service <1><SRVC> SOFTWARE CESR 500100
Configuration Ver. xxx
<> Unit Type 1 = Air-cooled,
2 = Water-cooled
x 3 = Split system
<> Number of Cir A Comp
x
<> Compressor A1 Tonnage
xx
<> Compress A2 Tonnage
xx
<> Capacity high 0 = Disabled
temperature override 1 = Enabled
x
<> Number of Cir B Comp
x
<> Compressor B1 Tonnage
xx
<> Compressor B2 Tonnage
xx
<> Max. Cond. Temp Setpoint 30GX = 70°C
xxx.x °C 30HXA = 70°C
30HXC = 50°C
<> MOP Setpoint Default = 11.1°C
xx.x °C
<> Fan Staging Select Displays Not Used
or a number
x
<> CPM Board Used?
Yes
<> Compr. A1 Must Trip Verify with
Amps Compressor
xxx.x Electrical Data
<> Compr. A2 Must Trip Verify with
Amps Compressor
xxx.x Electrical Data
<> Compr. B1 Must Trip Verify with
Amps Compressor
xxx.x Electrical Data
<> Compr. B2 Must Trip Verify with
Amps Compressor
xxx.x Electrical Data
2 Options <2><SRVC> COOLER FLUID SELECT 1 = Water (Default),
Configuration 1 2 = Medium Temp
brine
x 3 = Low Temp Brine
(HX only).
<> Min. Load Valve Select Displays Enable
Disable
x Default: Disable.
<> Loading Sequence Select 1 = Equal circuit.
2 = Staged circuit
x Default: 1
<> Lead/Lag Sequence Select 1 = Automatic
(Default),
2 = Circuit A leads,
x 3 = Circuit B leads
<> Head Press. Control Type 0 = None (Default),
1 = Air cooled,
x 2 = Water cooled,
3 = Fixed air cooled
<> Motormaster Select 0 = None (Default),
x 1 = Direct control
The use of the service function is reserved to the Carrier service
personal only.