Specifications

46
History function and subfunctions
HISTORY
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
1 Operating Hours <1> <HIST> Machine Operating Hours
xxx.x hours
<> Machine Starts
xxx
<> Circuit A
<> Operating hours
xxx.x hours
<> Compressor A1 Hours
xxx.x hours
<> Compressor A2 Hours
xxx.x hours
<> Starts
<> Compressor A1 Starts
xxx
<> Compressor A2 Starts
xxx
<> Circuit B
<> Operating hours
xxx.x hours
<> Compressor B1 Hours
xxx.x hours
<> Compressor B2 Hours
xxx.x hours
<> Starts
<> Compressor B1 Starts
xxx
<> Compressor B2 Starts
xxx
2 Alarm History <2> <HIST> PREVIOUS ALARM 1 - Lists 10 most
description recent alarms.
Alarm description time/ Use EXPN key when
day of occurence necessary
<> Previous Alarm 2 - description
Alarm description time/
day of occurence
<> Previous Alarm 3 - description
Alarm description time/
day of occurence
<> Previous Alarm 4 - description
Alarm description time/
day of occurence
<> Previous Alarm 5 - description
Alarm description time/
day of occurence
<> Previous Alarm 6 - description
Alarm description time/
day of occurence
<> Previous Alarm 7 - description
Alarm description time/
day of occurence
<> Previous Alarm 8 - description
Alarm description time/
day of occurence
<> Previous Alarm 9 - description
Alarm description time/
day of occurence
<> Previous Alarm 10 - description
Alarm description time/
day of occurence
SERVICE (CONT.)
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
5 Factory <5> <SRVC> COOLING RESET TYPE 1
Configuration codes <> Configuration code 1 Factory set
xxxxxxxx
<> Configuration code 2 Factory set
xxxxxxxx
<> Configuration code 3 Factory set
xxxxxxxx
<> SERVICE CODES
<> Configuration code 4 Factory set
xxxxxxxx
<> Configuration code 5 Factory set
xxxxxxxx
6 NOT USED
7 Transducer <7> <SRVC> CALIBRATION OFFSET
calibration <> CIRCUIT A PRESSURE
<> Discharge pressure
xxx.x kPa
<> Suction pressure
xxx.x kPa
<> A1 oil pressure
xxx.x kPa
<> A2 oil pressure
xxx.x kPa
<> Economizer pressure
xxx.x kPa
<> CALIBRATION OFFSET
<> CIRCUIT B PRESSURE
<> Discharge pressure
xxx.x kPa
<> Suction pressure
xxx.x kPa
<> B1 oil pressure
xxx.x kPa
<> B2 oil pressure
xxx.x kPa
<> Economizer pressure
xxx.x kPa
<> Calibrate all at 0 kPa
Yes/No
<> Last calibration date
mmm dd - yy
8 Manual control <8> <SRVC> Manual control enable LOR switch should
table Dsable be in OFF position
<1> <ENTR> Password protected Will be displayed if
Enter: not entered earlier
in current HSIO use
<1111> <ENTR> Manual control enable
Dsable
<1> <ENTR> Manual control enable Switch LOR switch
Enable to local before
proceeding
<> Circuit A compressor 1
Off
<> <1> <ENTR> Circuit A compressor 1 Provided no alarms
On exist, control will
attempt circuit start
within 2 minutes.
Press <0> <ENTR>
to stop circuit
<> Circuit A compressor 2 <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
<> Circuit A loader 1 <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
<> Circuit A loader 2 <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
<> Circuit A hot gas bypass <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
<> Circuit B compressor 1 <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
SERVICE (CONT.)
SUBFUNCTION KEYPAD DISPLAY COMMENT
ENTRY
<> Circuit B compressor 1 <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
<> Circuit B loader 1 <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
<> Circuit B loader 2 <1> <ENTR>
Off to enable,
<0> <ENTR> to stop
<> Circuit B hot gas bypass <1> <ENTR>
Off to enable,
<0> <ENTR> to stop