Specifications

5
DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION
30HXC 075-185
NOTE : Refer to certified dimensional drawings 99DI 075HX when designing an installation.
P1
ØS
ØR
P3
P2 P4
13
14
34 34
33
15
33
10
1
30HXC ABCDEFGHJKLMNØRØS
075-095 2730 1775 875 1217 1220 222.5 332 268.3 265.4 2360 1000 593 279 114.3 139.7
105 2730 1825 875 1217 1220 222.5 332 276.5 300 2360 1000 593 279 139.7 139.7
115-145 3535 1775 1035 1635 1220 222.5 332 286 230 3220 1000 593 734 19.7 139.7
160-170 3550 1900 1195 1635 1328 306 257 340 300 3220 1000 620 804 139.7 168.3
185 3550 1900 1195 1635 1328 306 257 360 260 3220 1000 620 804 168.3 168.3
Weight distribution Total
at the four operating
mounting holes (kg) weight (kg)
30HXC P1 P2 P3 P4 PT
075 703 613 634 553 2503
085 707 617 637 557 2518
095 719 627 647 567 2560
105 767 670 691 603 2731
115 795 695 716 627 2833
125 807 705 726 634 2872
135 830 726 746 654 2956
145 835 730 750 656 2971
160 922 808 818 735 3283
170 936 848 848 771 3403
185 968 876 876 797 3517
Legend :
Services clearances required
Space required to remove
cooler and condenser tubes
Electrical supply entry