Specifications

60
START-UP CKECKLIST FOR 30HXC/GX LIQUID CHILLERS (USE FOR JOB FILE)
Preliminary information
Job name: ................................................................................................................................................................................................
Location: .................................................................................................................................................................................................
Installing contractor:...............................................................................................................................................................................
Distributor:..............................................................................................................................................................................................
Start-up preformed by: ...........................................................................................................................................................................
Equipment
Model:............................................................................................. S/N ..............................................................................................
Compressors
Circuit A Circuit B
1. Model # ...................................................................................... 1. Model # .................................................................................
S/N ............................................................................................. S/N ..............................................................................................
Mtr #........................................................................................... Mtr # ...........................................................................................
2. Model # ...................................................................................... 2. Model # .................................................................................
S/N ............................................................................................. S/N ..............................................................................................
Mtr #........................................................................................... Mtr # ...........................................................................................
Cooler
Model #........................................................................................... Manufactured by .........................................................................
S/N .................................................................................................. Date .............................................................................................
Condenser (30HXC)
Model #........................................................................................... Manufactured by .........................................................................
S/N .................................................................................................. Date .............................................................................................
Air handling equipment
Manufacturer ..........................................................................................................................................................................................
Model #........................................................................................... S/N ..............................................................................................
Additional air handling units and accessories ........................................................................................................................................
................................................................................................................................................................................................................
Preliminary equipment check
Is there any shipping damage ?....................................................... If so, where ?...............................................................................
................................................................................................................................................................................................................
Will this damage prevent unit start-up ? .................................................................................................................................................
Unit is level in its installation
Power supply agrees with the unit nameplate
Electrical circuit wiring has been sized and installed properly
Unit ground wire has been connected
Electrical circuit protection has been sized and installed properly
All terminals are tight
All cables and thermistors have been inspected for crossed wires
All plug assemblies are tight
Check air handling systems
All air handlers are operating
All chilled water valves are open
All fluid piping is connected properly
All air has been vented from the system
Chilled water pump (CWP) is operating with the correct rotation. CWP amperage: Rated:............. Actual ...............