Specifications

9
DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (CONT.)
30GX 175
NOTE : Refer to certified dimensional drawings 99DI 175GX when designing an installation.
Notes :
1. Unit must have clearances for air flow as follows :
Top : do not restrict in any way
End and Side space required (from solid surface)
2. In case of multiple chillers (up to four units), the respective
clearance between them should be increased from 1830 to
2000 mm for the side space requirement.
3. Unit must have clearances for cooler tube removal as
follows :
Additional space required to remove cooler tubes
Electrical box
2000
1830
2000
1830
20002000
1525
1525
Multiple chiller installation (see note 2)
SOLID SURFACE AREASOLID SURFACE AREA
Weight distribution Total
at the ten operating
mounting holes (kg) weight (kg)
30GX P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 PT
175 506 323 322 635 467 687 527 702 321 181 4671