Specifications

INSTANTANEOUSANDINTEGRATEDHEATINGRATINGS(cont)
SYSTEM35H*CEILING-SUSPENDEDSYSTEM(38QR-C0363-PHASEUNITWITH40QAE036)
TEMP (F)
AIR
ENTERING
INDOOR UNIT
AIR
ENTERING
INDOOR UNIT
(CFM)
AIR TEMPERATURE ENTERING OUTDOOR COIL (F)
010172030404760
55
630
Cap 14.40 13.20 18.00 16.50 20.60 18.80 21.90 19.70 26.20 23.00 31.00 31.00 34.70 34.70 41.80 41.80
kW 2.51 2.67 2.79 2.84 3.00 3.17 3.29 3.52
750
Cap 14.90 13.70 18.60 17.00 21.30 19.40 22.60 20.40 27.10 23.80 32.30 32.30 36.00 36.00 42.10 42.10
kW 2.52 2.67 2.77 2.82 2.96 3.11 3.21 3.28
870
Cap 15.20 14.00 19.10 17.50 21.80 19.90 23.20 20.90 27.90 24.40 33.10 33.10 36.40 36.40 42.50 42.50
kW 2.54 2.67 2.77 2.81 2.94 3.07 3.11 3.18
60
630
Cap 13.70 12.60 17.40 15.90 20.00 18.20 21.20 19.20 25.50 22.30 30.20 30.20 33.80 33.80 40.80 40.80
kW 2.53 2.70 2.82 2.88 3.05 3.22 3.35 3.58
750
Cap 14.20 13.00 18.00 16.40 20.60 18.80 21.90 19.80 26.40 23.10 31.40 31.40 35.20 35.20 41.60 41.60
kW 2.54 2.70 2.81 2.86 3.02 3.17 3.27 3.39
870
Cap 14.50 13.40 18.40 16.80 21.10 19.30 22.50 20.30 27.10 23.80 32.30 32.30 35.80 35.80 42.20 42.20
kW 2.56 2.71 2.81 2.86 2.99 3.13 3.19 3.30
65
630
Cap 13.00 11.90 16.70 15.30 19.30 17.60 20.60 18.60 24.80 21.70 29.40 29.40 33.00 33.00 39.80 39.80
kW 2.54 2.73 2.86 2.91 3.09 3.28 3.40 3.64
750
Cap 13.50 12.40 17.30 15.80 20.00 18.20 21.30 19.20 25.60 22.50 30.60 30.60 34.30 34.30 41.10 41.10
kW 2.56 2.73 2.85 2.90 3.07 3.23 3.34 3.51
870
Cap 13.80 12.70 17.70 16.20 20.50 18.70 21.80 19.70 26.30 23.10 31.40 31.40 35.10 35.10 42.00 42.00
kW 2.58 2.74 2.86 2.90 3.05 3.20 3.28 3.43
70
630
Cap 12.30 11.30 16.10 14.70 18.70 17.00 19.90 18.00 24.00 21.10 28.60 28.60 32.10 32.10 38.80 38.80
kW 2.56 2.76 2.89 2.95 3.14 3.33 3.46 3.70
750
Cap 12.80 11.70 16.60 15.20 19.30 17.60 20.60 18.60 24.90 21.80 29.70 29.70 33.40 33.40 40.50 40.50
kW 2.59 2.77 2.89 2.95 3.12 3.29 3.41 3.63
870
Cap 13.10 12.10 17.10 15.60 19.80 18.10† 21.10 19.10 25.60 22.40 30.60 30.60 34.40 34.40† 41.70 41.70
kw 2.61 2.78 2.90 2.95 3.10 3.26 3.36 3.55
75
630
Cap 11.50 10.60 15.40 14.00 18.00 16.40 19.20 17.40 23.30 20.40 27.80 27.80 31.20 31.20 37.80 37.80
kW 2.58 2.78 2.92 2.98 3.18 3.38 3.51 3.76
750
Cap 12.00 11.10 15.90 14.60 18.70 17.00 19.90 18.00 24.20 21.20 28.90 28.90 32.50 32.50 39.50 39.50
kW 2.60 2.79 2.93 2.98 3.17 3.34 3.46 3.69
870
Cap 12.40 11.40 16.40 15.00 19.10 17.50 20.40 18.40 24.80 21.70 29.80 29.80 33.50 33.50 40.80 40.80
kW 2.63 2.81 2.94 2.99 3.16 3.32 3.43 3.62
80
630
Cap 10.80 9.94 14.70 13.40 17.40 15.80 18.60 16.70 22.60 19.80 27.00 27.00 30.40 30.40 36.90 36.90
kW 2.59 2.80 2.95 3.01 3.22 3.43 3.57 3.82
750
Cap 11.30 10.40 15.20 13.90 18.00 16.40 19.20 17.40 23.40 20.50 28.10 28.10 31.60 31.60 38.40 38.40
kW 2.62 2.82 2.96 3.02 3.21 3.40 3.52 3.75
870
Cap 11.60 10.70 15.70 14.30 18.50 16.80 19.80 17.80 24.10 21.10 28.90 28.90 32.60 32.60 39.80 39.80
kW 2.64 2.84 2.97 3.03 3.21 3.37 3.50 3.69
Indicates rating condition.
Indicates integrated rating.
LEGEND
Cap Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
kW Total Power Input (includes compressor motor power input, outdoor-
fan motor power input, and indoor-fan motor power input)
*Click here to view SystemsIndexTable.
†Integrated Rating.
NOTE: Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the
outdoor coil and the heat required to defrost it.