Specifications

COOLINGCAPACITIES(cont)
TABLENO.45*38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITH
TWO40QNB018HIGHWALLUNITS
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR CFM/BF
720/0.12 828/0.13 900/0.15
Air Entering Evaporator Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 22.8 23.7 25.8 28.0 23.8 24.3 26.4 28.6 24.8 25.0 27.0 29.2
SHG 22.8 21.3 17.8 14.2 23.8 22.8 18.9 14.9 24.8 24.4 20.2 15.7
TC 22.5 23.5 25.6 27.8 23.5 24.1 26.1 28.3 24.4 24.6 26.6 28.8
kW 1.31 1.31 1.31 1.32 1.32 1.32 1.32 1.33 1.34 1.34 1.34 1.34
CMP 1.10 1.10 1.10 1.10 1.10 1.10 1.10 1.11 1.10 1.10 1.10 1.11
65
TCG 22.2 23.0 25.0 27.1 23.1 23.6 25.6 27.7 24.1 24.2 26.1 28.2
SHG 22.2 20.9 17.4 13.9 23.1 22.4 18.6 14.6 24.1 23.9 19.9 15.4
TC 21.9 22.7 24.8 26.9 22.8 23.3 25.3 27.4 23.7 23.9 25.7 27.9
kW 1.45 1.45 1.45 1.46 1.46 1.46 1.47 1.47 1.48 1.48 1.48 1.49
CMP 1.24 1.24 1.24 1.25 1.24 1.24 1.24 1.25 1.24 1.24 1.24 1.25
75
TCG 21.6 22.2 24.2 26.2 22.5 22.8 24.7 26.7 23.4 23.4 25.2 27.2
SHG 21.6 20.5 17.1 13.5 22.5 21.9 18.2 14.2 23.4 23.3 19.5 15.0
TC 21.3 22.0 23.9 26.0 22.2 22.5 24.4 26.5 23.0 23.1 24.8 26.9
kW 1.61 1.61 1.62 1.62 1.62 1.62 1.63 1.64 1.64 1.64 1.64 1.65
CMP 1.40 1.40 1.40 1.41 1.40 1.40 1.40 1.41 1.40 1.40 1.41 1.41
85
TCG20.921.423.325.321.822.023.825.822.622.624.326.3
SHG 20.9 20.1 16.7 13.2 21.8 21.5 17.9 13.9 22.6 22.6 19.1 14.7
TC 20.7 21.2 23.1 25.1 21.5 21.7 23.5 25.5 22.3 22.3 23.9 25.9
kW 1.79 1.79 1.80 1.81 1.81 1.81 1.81 1.82 1.82 1.82 1.83 1.84
CMP 1.58 1.58 1.59 1.60 1.58 1.58 1.59 1.60 1.58 1.59 1.59 1.60
95
TCG 20.3 20.7 22.5 24.4 21.1 21.2 22.9 24.8 21.9 21.9 23.3 25.3
SHG 20.3 19.7 16.4 12.9 21.1 21.0 17.5 13.5 21.9 21.9 18.8 14.3
TC 20.0 20.4 22.2 24.1 20.8 20.9 22.6 24.5 21.6 21.6 23.0 24.9
kW 2.00 2.00 2.01 2.02 2.01 2.01 2.02 2.03 2.03 2.03 2.03 2.05
CMP 1.79 1.79 1.80 1.80 1.79 1.79 1.80 1.81 1.79 1.79 1.80 1.81
105
TCG 19.7 19.9 21.6 23.5 20.4 20.5 22.0 23.9 21.2 21.2 22.4 24.3
SHG 19.7 19.3 16.0 12.5 20.4 20.4 17.2 13.2 21.2 21.2 18.4 14.0
TC 19.4 19.7 21.4 23.2 20.2 20.2 21.7 23.6 20.9 20.9 22.1 23.9
kW 2.23 2.23 2.24 2.25 2.25 2.25 2.26 2.27 2.26 2.27 2.27 2.28
CMP 2.02 2.02 2.03 2.04 2.02 2.02 2.03 2.04 2.03 2.03 2.03 2.05
115
TCG 19.0 19.2 20.8 22.5 19.8 19.8 21.2 22.9 20.5 20.5 21.5 23.3
SHG 19.0 18.9 15.7 12.2 19.8 19.8 16.8 12.8 20.5 20.5 18.1 13.6
TC 18.8 18.9 20.5 22.3 19.5 19.5 20.9 22.6 20.2 20.2 21.2 22.9
kW 2.50 2.50 2.51 2.52 2.51 2.51 2.52 2.54 2.53 2.53 2.54 2.55
CMP 2.28 2.28 2.30 2.31 2.29 2.29 2.30 2.31 2.29 2.30 2.30 2.32
125
TCG 18.4 18.4 19.9 21.6 19.1 19.1 20.3 21.9 19.8 19.8 20.6 22.3
SHG 18.4 18.4 15.4 11.9 19.1 19.1 16.4 12.5 19.8 19.8 17.7 13.3
TC 18.1 18.2 19.6 21.3 18.8 18.8 20.0 21.6 19.4 19.4 20.2 21.9
kW 2.80 2.80 2.81 2.83 2.81 2.81 2.83 2.84 2.83 2.84 2.84 2.86
CMP 2.58 2.58 2.60 2.62 2.59 2.59 2.60 2.62 2.60 2.60 2.60 2.62
Rating condition.
LEGEND
BF Bypass Factor
CMP Compressor Power
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Total Power (Includes CMP)
SHG Gross Sensible Capacity (1000 Btuh)
TC Total Net Cooling Capacity (1000 Btuh)
TCG Gross Cooling Capacity (1000 Btuh)
*Click here to view SystemsIndexTable.
Many multi-split systems require the use of more than one cooling ca-
pacity table to determine system total capacity and power.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 BF) x (edb 80).