Specifications

COOLINGCAPACITIES(cont)
TABLENO.54*38HDS024(or1Circuitof38HDS048System)CONDENSINGUNITWITH
ONE40QKB036IN-CEILINGCASSETTEUNIT
TEMP (F)
AIR ENTERING
CONDENSER
(Edb)
AIR ENTERING EVAPORATOR CFM/BF
635/0.08 745/0.10 915/0.12
Air Entering Evaporator Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
55
TCG 26.7 28.5 30.1 31.7 28.0 29.2 30.9 32.1 29.4 29.9 31.8 33.0
SHG 26.7 23.7 19.4 15.5 28.0 25.3 20.6 16.0 29.4 27.3 22.1 16.8
TC 26.3 28.0 29.6 31.2 27.4 28.7 30.4 31.6 28.8 29.2 31.2 32.3
kW 2.14 2.15 2.16 2.18 2.18 2.19 2.20 2.21 2.24 2.24 2.26 2.27
CMP 1.71 1.72 1.73 1.75 1.72 1.73 1.74 1.75 1.73 1.73 1.75 1.76
65
TCG 25.2 26.7 29.0 30.4 26.5 27.5 29.7 31.1 27.9 28.4 30.3 31.9
SHG 25.2 22.6 19.0 15.0 26.5 24.4 20.2 15.6 27.9 26.7 21.6 16.5
TC 24.8 26.2 28.6 30.0 26.0 27.0 29.2 30.6 27.3 27.7 29.6 31.3
kW 2.16 2.16 2.18 2.19 2.19 2.20 2.22 2.23 2.25 2.25 2.27 2.29
CMP 1.76 1.77 1.79 1.80 1.77 1.78 1.80 1.81 1.78 1.78 1.80 1.82
75
TCG 23.5 24.8 27.1 28.7 24.8 25.6 27.8 29.4 26.2 26.5 28.4 30.3
SHG 23.5 21.5 18.0 14.2 24.8 23.2 19.2 14.9 26.2 25.5 20.8 15.9
TC 23.1 24.4 26.7 28.3 24.3 25.1 27.3 28.9 25.6 25.9 27.8 29.7
kW 2.15 2.16 2.18 2.19 2.19 2.19 2.21 2.23 2.24 2.24 2.26 2.28
CMP 1.79 1.80 1.82 1.83 1.80 1.81 1.83 1.84 1.81 1.82 1.83 1.85
85
TCG 21.9 23.0 25.1 27.0 23.1 23.7 25.8 27.8 24.5 24.7 26.6 28.6
SHG 21.9 20.3 17.0 13.5 23.1 22.0 18.2 14.3 24.5 24.3 19.9 15.3
TC 21.5 22.6 24.7 26.6 22.6 23.3 25.4 27.3 23.9 24.1 26.0 28.0
kW 2.14 2.16 2.17 2.19 2.18 2.18 2.20 2.22 2.22 2.23 2.24 2.27
CMP 1.82 1.83 1.85 1.87 1.84 1.84 1.86 1.88 1.84 1.85 1.86 1.89
95
TCG 20.2 21.1 23.2 25.1 21.4 21.8 23.8 25.8 22.7 22.8 24.5 26.6
SHG 20.2 19.0 16.0 12.7 21.4 20.7 17.1 13.4 22.7 22.7 18.9 14.5
TC 19.9 20.7 22.8 24.7 20.9 21.3 23.4 25.3 22.2 22.2 24.0 26.0
kW 2.10 2.11 2.13 2.15 2.13 2.14 2.16 2.18 2.18 2.18 2.20 2.23
CMP 1.82 1.83 1.85 1.87 1.83 1.84 1.85 1.88 1.85 1.85 1.86 1.89
105
TCG 18.6 19.3 21.3 23.2 19.7 19.9 21.9 23.8 20.9 20.9 22.5 24.5
SHG 18.6 17.7 14.9 11.9 19.7 19.3 16.1 12.5 20.9 20.9 17.7 13.6
TC 18.3 18.9 20.9 22.9 19.3 19.5 21.4 23.3 20.4 20.4 22.0 24.0
kW 2.03 2.04 2.07 2.09 2.06 2.07 2.09 2.11 2.11 2.11 2.12 2.15
CMP 1.78 1.79 1.82 1.84 1.80 1.80 1.83 1.84 1.81 1.81 1.83 1.86
115
TCG 17.1 17.6 19.4 21.3 18.1 18.2 19.9 21.8 19.2 19.2 20.5 22.4
SHG 17.1 16.5 13.8 11.0 18.1 17.9 15.0 11.7 19.2 19.2 16.6 12.7
TC 16.8 17.3 19.1 21.0 17.7 17.8 19.5 21.4 18.7 18.7 20.0 21.9
kW 1.89 1.90 1.93 1.96 1.93 1.93 1.95 1.98 1.97 1.97 1.99 2.01
CMP 1.68 1.69 1.72 1.75 1.70 1.70 1.73 1.75 1.72 1.72 1.74 1.76
125
TCG 15.6 15.9 17.5 19.4 16.5 16.5 18.0 19.8 17.5 17.5 18.5 20.4
SHG 15.6 15.3 12.8 10.1 16.5 16.5 13.8 10.8 17.5 17.5 15.4 11.8
TC 15.3 15.6 17.2 19.0 16.1 16.1 17.6 19.4 17.0 17.0 18.1 19.9
kW 1.76 1.77 1.80 1.83 1.79 1.79 1.82 1.84 1.83 1.83 1.85 1.87
CMP 1.59 1.59 1.62 1.65 1.60 1.60 1.63 1.66 1.62 1.62 1.64 1.67
Rating condition.
LEGEND
BF Bypass Factor
CMP Compressor Power
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW Total Power (Includes CMP)
SHG Gross Sensible Capacity (1000 Btuh)
TC Total Net Cooling Capacity (1000 Btuh)
TCG Gross Cooling Capacity (1000 Btuh)
*Click here to view SystemsIndexTable.
Many multi-split systems require the use of more than one cooling ca-
pacity table to determine system total capacity and power.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHG.
Above 80 F edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 BF) x (edb 80).