Product Data 38/40BN Series Duct-Free Split Systems Cooling Only and Heat Pumps for High-Wall Applications 11/2 to 3 Nominal Tons The Ideal Complement to Your Ducted System When It Is Impractical or Prohibitively Expensive to Use Ductwork Features/Benefits An inexpensive and creative solution to design problems INDOOR UNIT OUTDOOR UNIT Copyright 2004 Carrier Corporation The 38/40BN series duct-free split systems are a matched combination of an outdoor condensing unit and an indoor fan coil units conn
The 38/40BN duct-free split systems offer the solution of choice. The compressor is outdoors, linked by refrigerant lines to an indoor fan coil located directly in the room it will heat or cool. These systems have minimal impact on the existing structure, and the design and interior of the conditioned space is not compromised by bulky ductwork. Because of these features, this duct-free split system can be installed in places where conventional ducted cooling simply cannot go.
Features/Benefits (cont) Economical operation The duct-free split system design allows individual room heating or cooling only where required. There is no need to run large supply-air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted moving air through ducts. Features like the rifled copper tube with louvered aluminum plate fin coil provide maximum heat transfer.
Model number nomenclature OUTDOOR UNIT 38 BNB 018 – 3 Voltage 3 – 208/230-1-60 Air-Cooled Condenser Nominal Capacity 018 – 1-1/2 Tons 024 – 2 Tons 030 – 2-1/2 Tons 036 – 3 Tons Unit Type BNB – Cooling Only BNE – Heat Pump INDOOR UNIT 40 4 BNB 018 – 3 Indoor Fan Coil Voltage 3 – 208/230-1-60 Unit Type BNB – High Wall Cooling Only BNE – High Wall Heat Pump Nominal Capacity 018 – 1-1/2 Tons 024 – 2 Tons 030 – 2-1/2 Tons 036 – 3 Tons
ARI* capacity ratings ARI CAPACITIES HIGH-WALL APPLICATIONS INDOOR SECTION OUTDOOR SECTION 40BNB018-3 40BNB024-3 40BNB030-3 40BNB036-3 40BNE018-3 40BNE024-3 40BNE030-3 40BNE036-3 38BNB018-3 38BNB024-3 38BNB030-3 38BNB036-3 38BNE018-3 38BNE024-3 38BNE030-3 38BNE036-3 COP — db — EER — HSPF — SEER — wb — STD. CFM Indoor Outdoor 726 1,100 726 2,400 700 2,300 970 2,300 726 1,100 726 2,400 700 2,300 970 2,300 NET COOLING BTUH TOTAL kW SEER EER 18,600 22,600 28,000 33,000 18,600 22,600 28,000 33,000 1.
Physical data INDOOR HIGH WALL UNITS COOLING AND HEAT PUMP MODELS UNIT NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) MOISTURE REMOVAL (pts/hr) REFRIGERANT TYPE METERING DEVICE CHARGE (lb) NOTE 1 INDOOR FAN (Direct Drive) High — CFM Med — CFM Low — CFM Motor Horsepower REFRIGERANT LINES Connection Type Liquid Line (in.) Vapor Line (in.) Max Length, Lift & Drop (ft) CONDENSATE DRAIN Outside Dia (in.
OUTDOOR UNITS COOLING ONLY MODELS UNIT NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) REFRIGERANT TYPE METERING DEVICE CHARGE (lb) OUTDOOR FAN CFM High/Low Horsepower REFRIGERANT LINES Connection Type Liquid Line (in.) Vapor Line (in.) Max Length (ft) Max Lift (ft) Max Drop (ft) COMPRESSOR Manufacturer Model Type Oil Charge (oz) Heater Accumulator CONTROLS Control Voltage System Voltage Defrost Method FINISH 38BNB018 1.5 143 R-22 Cap Tube 3.1 38BNB024 2.0 187 R-22 Cap Tube 3.8 38BNB036 3.
Base unit dimensions — indoor unit, size 018,024 8
Base unit dimensions — indoor unit, size 030 9
Base unit dimensions — indoor unit, size 036 10
Base unit dimensions — outdoor unit 11
Electrical data INDOOR UNITS UNIT 40BNB 40BNE 018 .5 15 .4 FAN MOTOR AMPS .4 024 .5 15 .4 .4 030 .5 15 .4 .4 036 .8 15 .6 .6 018 .5 15 .4 .4 024 .5 15 .4 .4 030 .5 15 .4 .4 036 .8 15 .6 .6 SIZE MCA MOCP FLA COMPRESSOR AMPS COMPRESSOR LRA N/A N/A COMPRESSOR AMPS 7.4 COMPRESSOR LRA 48 OUTDOOR UNITS UNIT 38BNB 38BNE FLA LRA MCA MOCP — — — — SIZE MCA MOCP 018 11 15 8.2 FAN MOTOR AMPS 0.8 024 19 30 15.0 1.4 13.6 63 030 21 35 16.8 1.
Typical piping and wiring — high-wall WEATHERPROOF FUSED DISCONNECT† PER NEC 2 WIRES (+) GROUND AIRFLOW AIRFLOW OUTDOOR UNIT INSULATED LIQUID LINE INSULATED SUCTION LINE CONTROL CONNECTIONS WIRES† (5) HEAT PUMP (4) COOLING ONLY 2 WIRES (+) GROUND 24V CONTROL POWER PROVIDED INSIDE UNIT AIRFLOW S TA R T S TO P 1 2 3 SLEEP D A I LY MODE FAN SWEEP II I II I II II IIII II I I CONDENSATE DRAIN LINE† A A TIMER SET DEL AY CLEAR SENSE ROOM CLOCK FUSED DISCONNECT† WIRELESS CONTROLLER* TO
Application data Unit selection FAN COIL UNITS Select equipment to either match or be slightly less than anticipated peak load. This provides better humidity control, fewer unit cycles, and less part-load operation. For units used in spaces with high sensible loads, base equipment selection on unit sensible load, not on total anticipated load. Adjust for anticipated room wet bulb temperature to avoid undersizing equipment.
C CC CCH CCHT COMP FC GND IFM OFM RVS SW TB — — — — — — — — — — — — TH LEGEND Contactor Compressor Capacitor Crankcase Heater Crankcase Heater Thermostat Compressor Fan Capacitor Ground Indoor Fan Motor Outdoor Fan Motor Reversing Valve Solenoid Sweep Motor Terminal Block — Thermistor/Thermostat Terminal (Marked) Splice Terminal (Unmarked) Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring NOTES: 1.
C CC COMP FC GND IFM OFM RVS SW TB TH — — — — — — — — — — — Contactor Compressor Capacitor Compressor Fan Capacitor Ground Indoor Fan Motor Outdoor Fan Motor Reversing Valve Solenoid Sweep Motor Terminal Block Thermistor/Thermostat LEGEND Terminal (Marked) Splice Terminal (Unmarked) Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90° C wire or its equivalent.
C CC CCH COMP CT FC GND IFM OFM OL PFC RVS SW — — — — — — — — — — — — — Contactor Compressor Capacitor Crankcase Heater Compressor Current Transformer Fan Capacitor Ground Indoor Fan Motor Outdoor Fan Motor Overload Power Factor Capacitor Reversing Valve Solenoid Sweep Motor TB — Terminal Block TH — Thermistor/Thermostat TRAN — Transformer Terminal (Marked) Splice Terminal (Unmarked) Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring LEGEND NOTES: 1.
C CC COMP FC GND IFM OFM RVS SW TB TH — — — — — — — — — — — Contactor Compressor Capacitor Compressor Fan Capacitor Ground Indoor Fan Motor Outdoor Fan Motor Reversing Valve Solenoid Sweep Motor Terminal Block Thermistor/Thermostat LEGEND Terminal (Marked) Splice Terminal (Unmarked) Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90° C wire or its equivalent.
C CC COMP FC GND IFM OFM RVS SW TB TH — — — — — — — — — — — Contactor Compressor Capacitor Compressor Fan Capacitor Ground Indoor Fan Motor Outdoor Fan Motor Reversing Valve Solenoid Sweep Motor Terminal Block Thermistor/Thermostat LEGEND Terminal (Marked) Splice Terminal (Unmarked) Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90° C wire or its equivalent.
C CC COMP FC GND IFM OFM RVS SW TB TH — — — — — — — — — — — Contactor Compressor Capacitor Compressor Fan Capacitor Ground Indoor Fan Motor Outdoor Fan Motor Reversing Valve Solenoid Sweep Motor Terminal Block Thermistor/Thermostat LEGEND Terminal (Marked) Splice Terminal (Unmarked) Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90° C wire or its equivalent.
Controls The Duct Free System can be set up and operated from the remote control (provided). If the remote is misplaced, the system can be operated from the “Auto” setting on the unit. If temperature of room air is lower than set point, the system will operate in Heating mode. If temperature of room air is higher than set point, the system will operate in Cooling mode.
Controls (cont) NOTE: If placing the air deflector in a fixed position is chosen, the deflector stops at the angle in which it was located when the ON/OFF button was pressed. Programming time periods — The duct free system can be programmed to operate at desired levels. Be sure to set the clock before programming the system. NOTE: If unit is operating in Dehumidification mode the fan will only operate in Low speed and cannot be changed.
Guide specifications — indoor unit Fan Coil Units HVAC Guide Specifications Size range: 11/2 to 3 Ton Capacity Model Number: 40BNB, 40BNE Part 1 — General 1.01 SYSTEM DESCRIPTION Indoor, wall-mounted, direct-expansion fan coil to be matched with the 38BN condensing or heat pump units. 1.02 QUALITY ASSURANCE Unit shall be rated per ARI Standards 210/240 and listed in the ARI directory as a matched system. Units shall be UL listed for sale in the U.S.A. and Canada. 1.
Guide specifications — indoor unit (cont) H. Refrigerant Lines: The indoor units shall have rotatable refrigerant lines for penetration through the wall using flare connections. All units shall have flare connections and a 90-degree suction elbow shall be provided for rear connection. I. Special Features (Field Installed): Condensate Pump: The condensate pump shall remove condensate from the drain pan when gravity drainage cannot be used. 24 Pump shall be designed for quiet operation.
Guide specifications — outdoor unit Condensing Units HVAC Guide Specifications Size Range: 11/2 to 3 Ton Capacity Model Number: 38BNB, 38BNE Part 1 — General 1.01 SYSTEM DESCRIPTION A. Outdoor-mounted, air-cooled split system outdoor section suitable for on-the-ground, rooftop, wall hung, balcony, or under-deck installation. Unit shall consist of a scroll or reciprocating compressor, an air-cooled coil, propeller-type draw-thru outdoor fans, full refrigerant charge, and control box.
Guide specifications — outdoor unit (cont) c. Automatic outdoor-fan motor protection. d. Start capacitor and relay (single-phase units without scroll compressors). 2. Safeties: a. System diagnostics provided through indoor controls. b. Compressor motor current and temperature overload protection. c. Outdoor fan failure protection. H. Electrical Requirements: 1. All units shall operate on single-phase, 60 cycle power at 208/230 v. 2. Unit electrical power shall be a single point connection. 26 3.
Carrier Corporation • Syracuse, New York 13221 5-04A 2-04 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 New Book 2 Pg 28 Catalog No. 523-80120 Printed in U.S.A.