Product data
Duct Free Systems - Physical Data - 38 Series AN & BK Condensers
Cooling Only and Heat Pump Models
AN009 * AN012-1 * AN012-3 * BK009 * BK012 * BK018 * BK024 *
Nominal Capacity (Tons)
0.75 1.0 1.0 0.75 1.0 1.5 2.0
Operating Weight
55 62 62 61 67 154 167
Refrigerant Type
R-22 R-22 R-22 R-22 R-22 R-22 R-22
Metering Device
Capillary Capillary Capillary Note #1 Note #1 Note #2 Note #2
Charge (Lbs) Note #3
1.5 1.8 1.8 1.5 2.0 1.5 1.5
Outdoor Fan
RPM/CFM 850/750 850/750 850/750 850/756 850/756 850/1720 850/1720
Diameter 12.25" 12.25" 12.25" 12.25" 12.25" 18.0" 18.0"
No Blades 4 4 4 4 4 3 3
Watts 87 87 87 87 87 1/8 hp 1/8 hp
Coil Data
Face Area (sq ft) 3.5 3.5 3.5 3.5 3.5 6.1 6.1
No Rows 1 2 2 1 2 1.5 2
FPI 18 17 17 18 17 15 15
High Pressure (psig)
Cut-In n/a n/a n/a n/a n/a 320 +/-20 320 +/-20
Cut-Out n/a n/a n/a n/a n/a 426 +/-7 426 +/-7
Low Pressure
Cut-In n/a n/a n/a n/a n/a 22 +/-5 22 +/-5
Cut-Out n/a n/a n/a n/a n/a 7 +/-3 7 +/-3
Refrigerent Lines
Connection Type Male Flare Male Flare Male Flare Male Flare Male Flare Sweat/Flare Sweat/Flair
Liquid Line 1/4" od 1/4" od 1/4" od 1/4" od 1/4" od 3/8" od (F) 3/8" od (F)
Vapor Line 1/2" od 1/2" od 1/2" od 1/2" od 1/2" od 5/8" od (S) 5/8" od (S)
Max Length 50 50 50 50 50 50 50
Max Lift 30 30 30 30 30 30 30
Max Drop 30' 30' 30' 30 30' 30' 30'
Compressor
Manufacturer Daewoo Daewoo Daewoo Daewoo Daewoo Tecumseh Tecumseh
Model EAA090111A ECA130111H EBB120111A EBA095111H EBB130111H AW5519G AW5524G
Type Rotary Rotary Rotary Rotary Rotary Recip Recip
Oil Charge (oz) 10.1 10.1 10.1 10.1 10.1 30.0 30.0
Crankcase Heater None None None 40 Watts 40 Watts 19 Watts 19 Watts
Accumulator Yes Yes Yes Yes Yes Yes Yes
Controls
Fusible Plug (F) 210 210 210 210 210 210 210
Control Voltage 115v 115v 208/230v 115v 208/230v 24V 24V
System Voltage 115v 115v 208/230v 115v 208/230v 208/230v 208/230v
Defrost Method n/a n/a n/a Demand Demand Time/Temp** Time/Temp**
Finish
Beige Beige Beige White White Gray Gray
Notes: Legend
1) AccuRater at outdoor unit * These units may only be used with 40QNB/QNE/QNH fan coils.
2) AccuRater at outdoor unit for heating and indoor unit for cooling. ** Demand defrost when used with 40QNE
3) Cooling only units are shipped with a full factory charge.
Rev "B"
Heat Pump units are shipped with a holding charge
01/11/02