Specification Sheet

7
INSTALLATION CLEARANCES
Maintenance space
Left
side
Right
side
Strong and durable ceiling
Indoor unit
)mc03(ni8.11> )mc01(ni4>
>0.8in(2cm)
>
0.8in(2cm)
>
11.8in(30cm)
(ni
2.
8
>)mc052
Floor
Service access Ceiling
)gn
i
l
iec on
ne
h
W(
Ceiling opening size
Access Panel Ceiling opening size
Fig. 5 – Installation Clearances
MAINTENANCE CLEARANCES
>11.8in30cm
Service access
Service access
Unit
Width of the Unit
Coil Connection Area
Condensate Drain Piping Area
Condensate Pump Service Clearance
Sensor Service Clearance
B
Depth of unit
Access Panel
17.7 in (45cm) x 17.7 in (45cm)
7.8 in (20cm)
>11.81 in (30cm)
>4 in (10cm)
Bottom Return
Blower/Motor Service Clearance
Filter Service Clearance
Blower/Motor Service Clearance
PCB Board Service Clearance
Fig. 6 – Maintenance Clearances
Table 1—Maintenance Clearances
Capacity (Kbtu) B
9K 11.81in.(30cm)
12K 11.81in.(30cm)
18K 11.81in.(30cm)
24K 11.81in.(30cm)
36K 11.81in.(30cm)
48K 15.75in.(40cm)
58K 15.75in.(40cm)
NOTE: If installed above a hard lid ceiling, utilize a ceiling access panel the length and width of the unit, otherwise the blower components
and/or entire unit cannot be removed.
If a single access panel is desired, the minimum dimensions should be:
S Width: The width of the unit plus 2−inches on both sides
S Length: The length of the unit plus 18−inches on the connection end and 2−inches on the opposite end