Specifications
116
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — PRESSURES
MODE — SET POINTS
MODE — INPUTS
*The display text changes depending on the remote switch configuration (
Configuration
→
UNIT
→
RM.CF
). If
RM.CF
is set to 0 (No Remote
Switch), then the display text will be “On” or “Off.” If
RM.CF
is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or
“Unoccupied.” If
RM.CF
is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If
RM.CF
is set to 3 (Override Switch), then the display
text will be “No Override” or “Override.”
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
AIR.P
AIR PRESSURES
→
SP
Static Pressure "H2O SP
→
BP
Building Pressure "H2O BP
REF.P
REFRIGERANT PRESSURES
→
DP.A
Cir A Discharge Pressure PSIG DP_A
→
SP.A
Cir A Suction Pressure PSIG SP_A
→
DP.B
Cir B Discharge Pressure PSIG DP_B
→
SP.B
Cir B Suction Pressure PSIG SP_B
ITEM DESCRIPTION RANGE UNITS CCN POINT DEFAULT
OHSP
Occupied Heat Setpoint 55-80 dF OHSP 68
OCSP
Occupied Cool Setpoint 55-80 dF OCSP 75
UHSP
Unoccupied Heat Setpoint 40-80 dF UHSP 55
UCSP
Unoccupied Cool Setpoint 75-95 dF UCSP 90
GAP
Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
V. C.ON
VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
V. C.OF
VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
SASP
Supply Air Setpoint 45-75 dF SASP 55
SA.HI
Supply Air Setpoint Hi 45-75 dF SASP_HI 55
SA.LO
Supply Air Setpoint Lo 45-75 dF SASP_LO 60
SA.HT
Heating Supply Air Setpt 90-145 dF SASPHEAT 85
T.PRG
Tempering Purge SASP –20-80 dF TEMPPURG 50
T.CL
Tempering in Cool SASP 5-75 dF TEMPCOOL 5
T.V.OC
Tempering Vent Occ SASP –20-80 dF TEMPVOCC 65
T.V.UN
Tempering Vent Unocc. SASP –20-80 dF TEMPVUNC 50
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
GEN.I
GENERAL INPUTS
→
FLT.S
Filter Status Input DRTY/CLN FLTS forcible
→
G.FAN
Fan Request From IGC ON/OFF IGCFAN
→
REMT
Remote Input State * RMTIN forcible
→
E.SW
Economizer Control Input YES/NO ECOSW forcible
→
E.ENA
Remote Economizer Enable YES/NO ECONENBL forcible
→
E.OVR
Econo Position Override YES/NO ECOORIDE forcible
→
S.FN.S
Supply Fan Status Switch ON/OFF SFS forcible
→
DL.S1
Demand Limit Switch 1 ON/OFF DMD_SW1 forcible
→
DL.S2
Demand Limit Switch 2 ON/OFF DMD_SW2 forcible
FD.BK
COMPRESSOR FEEDBACK
→
CS.A1
Compressor A1 Feedback ON/OFF CSB_A1
→
CS.A2
Compressor A2 Feedback ON/OFF CSB_A2
→
CS.B1
Compressor B1 Feedback ON/OFF CSB_B1
→
CS.B2
Compressor B2 Feedback ON/OFF CSB_B2
STAT
THERMOSTAT INPUTS
→
G
Thermostat G Input ON/OFF G forcible
→
W1
Thermostat W1 Input ON/OFF W1 forcible
→
W2
Thermostat W2 Input ON/OFF W2 forcible
→
Y1
Thermostat Y1 Input ON/OFF Y1 forcible
→
Y2
Thermostat Y2 Input ON/OFF Y2 forcible
FIRE
FIRE-SMOKE INPUTS
→
FSD
Fire Shutdown Input ALARM/NORMAL FSD forcible
→
PRES
Pressurization Input ALARM/NORMAL PRES forcible
→
EVAC
Evacuation Input ALARM/NORMAL EVAC forcible
→
PURG
Smoke Purge Input ALARM/NORMAL PURG forcible
REL.H
RELATIVE HUMIDITY
→
OA.RH
Outside Air Rel. Humidity % OARH forcible
→
OA.EN
Outdoor Air Enthalpy OAE
→
OA.DP
OutsideAir Dewpoint Temp dF OADEWTMP
→
RA.RH
Return Air Rel. Humidity % RARH forcible
→
RA.EN
Return Air Enthalpy RAE
AIR.Q
AIR QUALITY SENSORS
→
IAQ.I
IAQ - Discrete Input HIGH/LOW IAQIN forcible
→
IAQ
IAQ - PPM Return CO2 IAQ forcible
→
OAQ
OAQ - PPM Return CO2 OAQ forcible
→
DAQ
Diff.Air Quality in PPM DAQ
→
IQ.P.O
IAQ Min.Pos. Override % IAQMINOV forcible
RSET
RESET INPUTS
→
SA.S.R
Supply Air Setpnt. Reset ^F SASPRSET forcible
→
SP.RS
Static Pressure Reset SPRESET forcible